Insulation Condition Monitoring of Epoxy Resins Solid Dielectric in GIS Using Characteristic Gases COS and CS2
|更新时间:2025-12-08
|
Insulation Condition Monitoring of Epoxy Resins Solid Dielectric in GIS Using Characteristic Gases COS and CS2
Vol. 43, Issue 8, Pages: 2551-2557(2017)
作者机构:
1. 武汉大学电气工程学院
2. 广州供电局有限公司
3. 国网电力科学研究院武汉南瑞有限责任公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2017,
Published:2017
稿件说明:
移动端阅览
周文俊, 乔胜亚, 郑宇, et al. Insulation Condition Monitoring of Epoxy Resins Solid Dielectric in GIS Using Characteristic Gases COS and CS2[J]. 2017, 43(8): 2551-2557.
DOI:
周文俊, 乔胜亚, 郑宇, et al. Insulation Condition Monitoring of Epoxy Resins Solid Dielectric in GIS Using Characteristic Gases COS and CS2[J]. 2017, 43(8): 2551-2557.DOI:
Insulation Condition Monitoring of Epoxy Resins Solid Dielectric in GIS Using Characteristic Gases COS and CS2
To improve the accuracy of chemical diagnosis method used for estimating the insulation conditions of basin insulators and other epoxy resins solid dielectric in GIS
creeping discharge and related verification tests are set up to study the evolving law of SF6 decomposition products under typical discharge defects on a small apparatus. It is found that COS
as an important characteristic gas related to epoxy resins discharge
is produced under stronger discharge than CS
2
. B3P86/6-31G(d
p)
a method of calculation based on quantum chemistry
is adopted to explore the generating mechanism and energy conditions of COS when partial discharges occur on the solid dielectric
in GIS. Carbon which is a component of COS derives from basin insulators and other epoxy resin solid dielectric
and the reactions of intermediate HCS and O2 as well as CS
2
and OH are two main pathways to generate COS. Experiments and theoretical calculations show that decomposed gas CS
2
has a high sensitivity in judging whether the discharge is related to the epoxy resin solid dielectric
CS
2
can be applied to diagnose faults related to creeping discharge on the epoxy resin. The generation of COS indicates that the discharge level on the epoxy spacer deepens
thus the decomposition products testing period should be shortened