Novel Pilot Protection Scheme for Distribution Networks with Inverter-interfaced Distributed Generators
|更新时间:2025-12-08
|
Novel Pilot Protection Scheme for Distribution Networks with Inverter-interfaced Distributed Generators
Vol. 43, Issue 10, Pages: 3453-3462(2017)
作者机构:
华南理工大学电力学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 October 2017,
Published:2017
稿件说明:
移动端阅览
HAN Bowen, WANG Gang, LI Haifeng, et al. Novel Pilot Protection Scheme for Distribution Networks with Inverter-interfaced Distributed Generators[J]. 2017, 43(10): 3453-3462.
DOI:
HAN Bowen, WANG Gang, LI Haifeng, et al. Novel Pilot Protection Scheme for Distribution Networks with Inverter-interfaced Distributed Generators[J]. 2017, 43(10): 3453-3462.DOI:
Novel Pilot Protection Scheme for Distribution Networks with Inverter-interfaced Distributed Generators
摘要
中小容量逆变型分布式电源(IIDG)分散接入使传统单源中压配电网变为多源网络
常规过电流保护难以适用
且基于电力电子接口的分布式电源外输出特性和故障暂态特性与同步发电机相比存在明显差异。为此
提出了适用于有功/无功解耦控制(PQ控制)IIDG的等值模型
该模型能够准确刻画出具备低电压穿越能力IIDG的电流输出特性和故障暂态特性。在此基础上
通过研究馈线公共联接点(PCC)正序电压计算值的分布特征
在PCC线路两侧无需增加额外设备的原则下
提出了适用于高渗透率IIDG分散灵活接入的配电网全线速动双端纵联保护方案
降低了多端保护对纵联通道的需求
提高了电网经济性。最后
通过PSCAD/EMTDC验证了所提等值模型的准确性以及保护方案的有效性。仿真结果表明
由该等值模型所获取的IIDG电流的最大相对计算误差≤5%
且所提保护方案不受IIDG出力、故障类型、故障位置等因素的影响。
Abstract
The decentralized integration of medium-and small-capacity inverter-interfaced distributed generator(IIDG) makes a radial medium-voltage distribution network to become a scattered multi-source system
and the conventional overcurrent protection will not be applicable for this complex system.What is worse
the current external characteristics and fault transient characteristics of those distributed generators connected to power grid by coupling with power electronics interface are greatly different from conventional synchronous generators.Therefore
we established an equivalent model firstly for those grid-connected IIDG using PQ control strategy.The equivalent model can not only describe IIDG’s current output characteristics during normal operation
but also accurately characterize its fault transient characteristics under low voltage ride through operation.Then
we analyzed the profile characteristics of the positive-sequence voltages at points of common coupling(PCCs) in detail.Thereby
we proposed a novel two-terminal pilot protection scheme for distribution network with high penetration IIDG
in which additional protective equipment needed not to be added at both sides of PCC.The proposed scheme reduces the pilot channel requirements for multi-terminal pilot protection
and thus improves the economic efficiency for power grid.Finally
the accuracy of the IIDG equivalent model and the feasibility of the proposed protection scheme were both verified by the PSCAD/EMTDC simulation platform.The test results indicate that the relative calculation error of the IIDG current that is obtained by the equivalent model is less than 5%; and the proposed protection is widely applicable to various conditions involving different IIDG penetrations