Analysis and Simulated Experiment for Port Disturbance Voltage Due to Switching Operation in GIS Substation
|更新时间:2025-12-08
|
Analysis and Simulated Experiment for Port Disturbance Voltage Due to Switching Operation in GIS Substation
Vol. 43, Issue 10, Pages: 3387-3395(2017)
作者机构:
1. 华北电力大学新能源电力系统国家重点实验室
2. 江苏省电力公司经济技术研究院
3. 国网江苏省电力公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 October 2017,
Published:2017
稿件说明:
移动端阅览
WU Hengtian, JIAO Chongqing, CUI Xiang, et al. Analysis and Simulated Experiment for Port Disturbance Voltage Due to Switching Operation in GIS Substation[J]. 2017, 43(10): 3387-3395.
DOI:
WU Hengtian, JIAO Chongqing, CUI Xiang, et al. Analysis and Simulated Experiment for Port Disturbance Voltage Due to Switching Operation in GIS Substation[J]. 2017, 43(10): 3387-3395.DOI:
Analysis and Simulated Experiment for Port Disturbance Voltage Due to Switching Operation in GIS Substation
Many intelligent devices for measuring and monitoring such as merging unit and intelligent terminals are located in the local control cabinet in the construction of the smart GIS substations.These devices inside are vulnerable to electromagnetic disturbance induced by disconnector switching operations.Mastering the characteristics of the port electromagnetic disturbance of these devices is important for the EMC evaluation and immunity measures.Consequently
we designed and proposed a simulated experiment platform.Using steep pulse as the source
we measured the following data : the voltages between GIS rod and shell at the beginning and terminal of the GIS pipe
the port voltage between GIS shell and ground
the port disturbance voltage on the simulated intelligent sensor side
and the port disturbance voltage on the simulated local cabinet side.The voltage waveforms were compared with IEC standard from time domain and frequency domain aspects and fully analyzed.It is validated that the voltages from this platform are representative of the port disturbance and are in accordance with IEC standard damping oscillation waveform.Also
they were compared with the disturbances of GIS substations.The results show that the characteristics of these waveforms are close to those of disturbances measured in GIS substations.Hence
this platform can produce disturbance voltages in line with the requirements of EMC immunity and protection technique of secondary equipment port.