Study on Fast Analysis Method Transient Fundamental Frequency Overvoltage of Wind Turbine Generators in Sending System when Serious Power Disturbances Occur in Large-capacity UHVDC
|更新时间:2025-12-08
|
Study on Fast Analysis Method Transient Fundamental Frequency Overvoltage of Wind Turbine Generators in Sending System when Serious Power Disturbances Occur in Large-capacity UHVDC
Vol. 43, Issue 10, Pages: 3300-3306(2017)
作者机构:
1. 西北电力调控分中心
2. 南京南瑞集团公司
3. 西安交通大学电气工程学院陕西省智能电网重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 October 2017,
Published:2017
稿件说明:
移动端阅览
CAO Shengshun, ZHANG Wenchao, WANG Meng, et al. Study on Fast Analysis Method Transient Fundamental Frequency Overvoltage of Wind Turbine Generators in Sending System when Serious Power Disturbances Occur in Large-capacity UHVDC[J]. 2017, 43(10): 3300-3306.
DOI:
CAO Shengshun, ZHANG Wenchao, WANG Meng, et al. Study on Fast Analysis Method Transient Fundamental Frequency Overvoltage of Wind Turbine Generators in Sending System when Serious Power Disturbances Occur in Large-capacity UHVDC[J]. 2017, 43(10): 3300-3306.DOI:
Study on Fast Analysis Method Transient Fundamental Frequency Overvoltage of Wind Turbine Generators in Sending System when Serious Power Disturbances Occur in Large-capacity UHVDC
with the rapid development of UHV technology and renewble energy generation
when serious power disturbances occur in the large-capacity UHVDCs
the wind turbine generators in sending systems will suffer from serious transient fundamental frequency overvoltage
which may cause many wind turbine generators to trip possibly.Aiming at the problem above
we analyzed the mechanism of the overvoltage throughly
then poposed a fast computational method for the ovevoltage
in which the complete differntial sensitivity formula for node voltage variation caused by load variation were derived.The results are verified with the Jiuquan-Hunan HVDC wind transmission case system.The results show that the proposed method can be adopted to assess the overvoltage of wind turbine generators due to serious power disturbance in UHVDC
the error can be reduced from 21% to 14% compared to the experienced method