Aiming at the shortcomings of the analysis of voltage characteristic mechanism of UHV half-wavelength AC transmission system
we explained the steady-state voltage and fault voltage characteristics in detail.Moreover
we analyzed the steady-state voltage characteristics of half-wavelength lines and their influencing factors based on the distributed parameter model.Distribution characteristics of charging power and reactive power loss along half-wavelength line were deduced and the maximum voltage and its position were solved.Then
based on the fault equivalent circuit
fault voltage characteristics along half-wavelength line influenced by different fault types and system strengths were analyzed
and the mechanism of severe faults due to series resonance was explained.The simulation results based on a real power system show that overload and low power factor lead to overvoltage under a steady state
and series resonance overvoltage occurs under faults in 100
4
00 km ranges away from terminals
verifying the correctness of the foregoing analysis.
Numerical Calculation on Very Fast Transient Overvoltage of UHV Gas Insulated Substation by Variable Gap Arc Model
Establishment of Key Parameter System for Condition Evaluation of Transmission Line Based on Association Rules and Principal Component Analysis
Health Effects of Extremely Low Frequency Electromagnetic Fields
Analysis and Prospect of Lightning Shielding Failure Evaluation Methods of Transmission Lines
Mechanism and Application of Lightning Protection Gap Extinguishing Power Frequency Arc Assisted by Explosion Shock Wave
Related Author
LI Shuang
JIN Xin
BI Haitao
LI Bin
LU Xuchen
YAN Yingjie
SHENG Gehao
CHEN Yufeng
Related Institution
Electric Power Research Institute, State Grid Liaoning Electric Power Company
Maintenance and Test Center of Ultra High Voltage Company of South Grid
Electric Power Research Institute of Shandong Power Supply Company of State Grid
Department of Electrical Engineering, Shanghai Jiao Tong University
Research Group of Biophysics and Medical Engineering, Zhejiang Provincial Key Laboratory of Bioelectromagnetics,School of Medicine, Zhejiang University