Analysis on Feasibility for Deeply Suppressing Switching Overvoltage in AC UHV Systems
|更新时间:2025-12-08
|
Analysis on Feasibility for Deeply Suppressing Switching Overvoltage in AC UHV Systems
Vol. 44, Issue 1, Pages: 210-217(2018)
作者机构:
清华大学电机工程与应用电子技术系电力系统及发电设备控制和仿真国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 January 2018,
Published:2018
稿件说明:
移动端阅览
HE Jinliang, WU Jinbo, MENG Pengfei, et al. Analysis on Feasibility for Deeply Suppressing Switching Overvoltage in AC UHV Systems[J]. 2018, 44(1): 210-217.
DOI:
HE Jinliang, WU Jinbo, MENG Pengfei, et al. Analysis on Feasibility for Deeply Suppressing Switching Overvoltage in AC UHV Systems[J]. 2018, 44(1): 210-217.DOI:
Analysis on Feasibility for Deeply Suppressing Switching Overvoltage in AC UHV Systems
Deeply suppressing the switching overvoltage of UHV systems will reduce the manufacturing cost and technical bottlenecks of UHV power apparatus.Based on the 1 000 kV UHV project from Huainan to Wannan
the switching overvoltages were numerically analyzed.The effects of suppressing the overvoltage for measurements were estimated
such as setting arresters on both ends
cooperation between arresters and closing resistance
setting a set of arresters in the middle of the line
and setting several sets of arresters along the line.The effects of above methods in suppressing the switching overvoltages were compared
and the feasibility was analyzed in aspects such as aging characteristics
the withstand capacity of power frequency overvoltage
and energy absorption capacity.On the baisis of advanced surge arrester technology
we can decrease the ov
ervoltage level from 1.6 U
0
1
.7 U
0
to 1.2 U
0
1
.3 U
0
(U
0
=898 kV)
to realize the target to deeply suppress the switching overvoltage.