Parameter Optimization of Commutation Failure Prevention and Control of UHVDC Hierarchical Connection to AC Grid System
|更新时间:2025-12-08
|
Parameter Optimization of Commutation Failure Prevention and Control of UHVDC Hierarchical Connection to AC Grid System
Vol. 44, Issue 1, Pages: 329-336(2018)
作者机构:
1. 中国电力科学研究院有限公司
2. 电网安全与节能国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 January 2018,
Published:2018
稿件说明:
移动端阅览
WANG Yixuan, ZHANG Xin, MU Qing, et al. Parameter Optimization of Commutation Failure Prevention and Control of UHVDC Hierarchical Connection to AC Grid System[J]. 2018, 44(1): 329-336.
DOI:
WANG Yixuan, ZHANG Xin, MU Qing, et al. Parameter Optimization of Commutation Failure Prevention and Control of UHVDC Hierarchical Connection to AC Grid System[J]. 2018, 44(1): 329-336.DOI:
Parameter Optimization of Commutation Failure Prevention and Control of UHVDC Hierarchical Connection to AC Grid System
In order to solve the problem that commutation failure prevention and control of UHVDC hierarchical connection to AC grid system cannot perfectly suppress the converter valve commutation failure on a non-fault level
we proposed an improved control strategy.Several parameters of commutation failure prevention and control were optimized.Meanwhile
we revised the following main parameters in the control logic:amplitude coefficient
voltage change control gain
self maintaining link time constant and prevention and control synergy degree of two voltage levels.By using the ADPSS electromechanical-electromagnetic hybrid simulation software
we simulated the actual power grid data.The results show that the improved control strategy can effectively suppress the UHVDC system inverter’s commutation failure on both voltage levels
for one non-fault level is caused by another with fault of AC network