Modeling and Analysis of Transient Stability of UHV Half-wavelength and DC Hybrid Transmission System
|更新时间:2025-12-08
|
Modeling and Analysis of Transient Stability of UHV Half-wavelength and DC Hybrid Transmission System
Vol. 44, Issue 1, Pages: 75-82(2018)
作者机构:
1. 天津大学智能电网教育部重点实验室
2. 中国电力科学研究院有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 January 2018,
Published:2018
稿件说明:
移动端阅览
ZHAO Qianyu, WANG Shouxiang, QIN Xiaohui, et al. Modeling and Analysis of Transient Stability of UHV Half-wavelength and DC Hybrid Transmission System[J]. 2018, 44(1): 75-82.
DOI:
ZHAO Qianyu, WANG Shouxiang, QIN Xiaohui, et al. Modeling and Analysis of Transient Stability of UHV Half-wavelength and DC Hybrid Transmission System[J]. 2018, 44(1): 75-82.DOI:
Modeling and Analysis of Transient Stability of UHV Half-wavelength and DC Hybrid Transmission System
We established a model for the stability analysis of hybrid UHV half-wavelength and DC transmission system based on the quasi-steady model of half-wavelength transmission system.Moreover
we studied the stable operation range of the half wavelength transmission line
and discussed the power angle stability of the hybrid system during DC commutation failure and DC blocking.Meanwhile
we studied the power fluctuation mechanism of half-wavelength system caused by DC commutation failure and DC blocking based on shock response model and step response model of the two-order system
respectively
and studied the feasibility of emergency power support for the system to improve the transient stability of the half wavelength interconnected system by taking the advantage of fast power response of DC transmission system.The electromechanical transient simulation of UHV half wavelength and DC hybrid system proves the correctness of the methodology for the analysis of system power fluctuation caused by DC commutation failure and DC blocking
and also verifies the effectiveness of emergency power support of DC to half-wavelength transmission lines.The study shows that the peak of the power fluctuation of the half-wavelength line is related to the oscillation frequency during DC commutation failure.It also comes to the conclusion that the less the DC locking power is
the greater the damping and the smaller the peak value of the wave.And the DC power modulation can improve the transient stability of the asynchronous network system.