Response Characteristics and Mechanism Analysis About Virtual Inertia Control of Wind Generators
|更新时间:2025-12-08
|
Response Characteristics and Mechanism Analysis About Virtual Inertia Control of Wind Generators
Vol. 44, Issue 4, Pages: 1302-1310(2018)
作者机构:
1. 武汉大学电气工程学院
2. 海军工程大学舰船综合电力技术国防科技重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 May 2018,
Published:2018
稿件说明:
移动端阅览
XING Pengxiang, SHI Qiaoming, WANG Gang, et al. Response Characteristics and Mechanism Analysis About Virtual Inertia Control of Wind Generators[J]. 2018, 44(4): 1302-1310.
DOI:
XING Pengxiang, SHI Qiaoming, WANG Gang, et al. Response Characteristics and Mechanism Analysis About Virtual Inertia Control of Wind Generators[J]. 2018, 44(4): 1302-1310.DOI:
Response Characteristics and Mechanism Analysis About Virtual Inertia Control of Wind Generators
Virtual inertia control is an efficient way for wind generators to participate in system frequency regulation.Based on the principle of PD virtual inertia control and the simplified model of frequency response of wind generators integrated system
the response characteristics and the mechanism of PD virtual inertia control were analyzed
and the quantitative relation between PD virtual inertia control and system frequency was deduced.It is indicated that PD virtual inertia control is a temporary frequency modulation process
and the proportional control has a direct effect on the minimum frequency
while the differential control mainly affects the frequency descent rate and the time to reach the minimum value.Experiments were performed in the laboratory
and the results indicated that the maximum frequency deviation reduced from 0.84 Hz to 0.59 Hz and the rotor speed of the wind turbine reduced from 15.7 rad/s to 13.4 rad/s respectively with the increase of the proportional control coefficient under the same load disturbance
while the frequency descent rate reduced with the increase of the differential control coefficient.The experimental results are in accordance with the theoretical analysis
and validity of the response characteristic and mechanism analysis are proved
which provide some references for the PD virtual inertia control on parameters setting and control method modification.