Artificial Contamination Test System and Contamination Characteristics of Insulator
|更新时间:2025-12-08
|
Artificial Contamination Test System and Contamination Characteristics of Insulator
Vol. 44, Issue 6, Pages: 1861-1869(2018)
作者机构:
1. 中国电力科学研究院有限公司
2. 华中科技大学强电磁工程与新技术国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 July 2018,
Published:2018
稿件说明:
移动端阅览
WAN Xiaodong, NAN Jing, XU Tao, et al. Artificial Contamination Test System and Contamination Characteristics of Insulator[J]. 2018, 44(6): 1861-1869.
DOI:
WAN Xiaodong, NAN Jing, XU Tao, et al. Artificial Contamination Test System and Contamination Characteristics of Insulator[J]. 2018, 44(6): 1861-1869.DOI:
Artificial Contamination Test System and Contamination Characteristics of Insulator
摘要
开展绝缘子积污特性研究对污秽外绝缘的设计和运行维护具有重要意义
利用人工积污特性试验装置开展模拟环境下的绝缘子积污试验
可在较短时间内获得绝缘子的积污特性。为此研制了新型人工模拟自然积污试验系统
实现了风、雨、雾、干燥、电压及污秽物浓度等因素的独立控制
提出了人工模拟自然积污的试验方法。人工积污试验结果表明
随着污秽浓度的增加绝缘子表面的积污量趋于饱和
随着风速从2.2 m/s升至7.5 m/s
绝缘子表面污秽度呈现先逐渐增大后减小的趋势
随着时间的增长绝缘子表面积污量呈现初期较为缓慢、中期加快、后期趋缓并逐渐饱和的趋势
相同运行环境下绝缘子下表面积污由重到轻依次为普通、双伞型、三伞型。
Abstract
Research on contamination characteristics is of importance to external insulation design and power system operation. Artificial contamination test apparatus may be used to carry out insulator simulation contamination tests
and contamination characteristics of the insulator can be obtained in a relatively short period.Consequently
we developed a new artificial natural contamination test system in which wind
rain
fog
drying
voltage and grime concentration can be controlled independently
and then proposed test methods of artificial simulation of natural contamination.Artificial contamination test result shows that the contamination amount of insulator surface becomes saturated as the the contamination concentration increases
and the insulator surface contamination degree first increases and then decreases as the wind speed increases from 2.2 m/s to 7.5 m/s. The increment in contamination amount of insulator surface is relatively slow at the initial stage
speeds up at the medium stage
slows down and tends to the gradual saturation at the late stage as time becomes longer. Under the same operating environment
insulator contamination(from the serious to the low) is on cap and pin standard disc insulators