Heating Characteristics of Deteriorated Porcelain Insulator Under Different Humidities
|更新时间:2025-12-08
|
Heating Characteristics of Deteriorated Porcelain Insulator Under Different Humidities
Vol. 44, Issue 6, Pages: 1741-1749(2018)
作者机构:
1. 华北电力大学电力工程系
2. 国网河北省电力有限公司检修分公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:10 July 2018,
Published:2018
稿件说明:
移动端阅览
LIU Yunpeng, ZHANG Kaiyuan, FU Weiping, et al. Heating Characteristics of Deteriorated Porcelain Insulator Under Different Humidities[J]. 2018, 44(6): 1741-1749.
DOI:
LIU Yunpeng, ZHANG Kaiyuan, FU Weiping, et al. Heating Characteristics of Deteriorated Porcelain Insulator Under Different Humidities[J]. 2018, 44(6): 1741-1749.DOI:
Heating Characteristics of Deteriorated Porcelain Insulator Under Different Humidities
Deteriorated insulators among strings potentially threaten the safety of power grid. Consequently
taking porcelain insulators as objectives
and utilizing infrared thermograph
we studied the influences of defective insulators of different impedance located on different positions of the strings under various relative humidity on detection. The thermal statics of insulator strings were subtracted and then plotted
heating patterns of defective strings were studied
and the simulation of the above was made by a finite element analysis software Comsol. The experimental results show that the deteriorated insulators at the high voltage position of the string are more easy to be detected
and deteriorated insulators of large impedance on zero voltage position or middle of the strings may lead to false examining. The relationship between temperature rise and its impedance is nonlinear
and the rise reaches its maximum when the impedance is 30 M?. Under Icontamination level
temperature rise will reach maximum when relative humidity variesfrom 70% to 80%
and temperature rise of the deteriorated insulators will decrease when relative humidity ascends to 90%