Internal Overvoltage and Insulation Coordination of Electrode Line in HVDC Project
|更新时间:2025-12-08
|
Internal Overvoltage and Insulation Coordination of Electrode Line in HVDC Project
Vol. 44, Issue 7, Pages: 2331-2337(2018)
作者机构:
1. 国网四川省电力公司电力科学研究院
2. 中国电力科学研究院有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 July 2018,
Published:2018
稿件说明:
移动端阅览
XIE Shijun, SU Shaochun, HE Huiwen, et al. Internal Overvoltage and Insulation Coordination of Electrode Line in HVDC Project[J]. 2018, 44(7): 2331-2337.
DOI:
XIE Shijun, SU Shaochun, HE Huiwen, et al. Internal Overvoltage and Insulation Coordination of Electrode Line in HVDC Project[J]. 2018, 44(7): 2331-2337.DOI:
Internal Overvoltage and Insulation Coordination of Electrode Line in HVDC Project
To reveal the formation mechanism of internal overvoltage of electrode line in HVDC
its influence factors
and distribution feature
an overvoltage analysis model of UHVDC transmission project was established in EMTDC/PSCAD. Based on simulation results
the relationship among the amplitude of internal overvoltage
the amplitude and the gradient of current flow through the electrode line was analyzed. It is revealed that the severe fluctuating of unbalance current in electrode lines during faults or conversion of operation mode is the main cause for internal overvoltage. The internal overvoltage is affected by the fault type
the fault position
and the length of electrode line. And its amplitude reduces linearly along the electrode line. Moreover
the optimized configuration method of insulation level of electrode line was discussed. A reasonable and economic method to determine the scales of parallel gaps in electrode line was proposed. At last
a series of suggestions on the design and maintain of electrode line was presented.