Determination of H2S in SF6 Decomposition Products by Ultraviolet Absorption Spectrometry
|更新时间:2025-12-08
|
Determination of H2S in SF6 Decomposition Products by Ultraviolet Absorption Spectrometry
Vol. 44, Issue 8, Pages: 2573-2579(2018)
作者机构:
1. 云南电网有限责任公司电力科学研究院
2. 武汉大学电气工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2018,
Published:2018
稿件说明:
移动端阅览
YANG Yuling, GUO Xinliang, CUI Zhaolun, et al. Determination of H2S in SF6 Decomposition Products by Ultraviolet Absorption Spectrometry[J]. 2018, 44(8): 2573-2579.
DOI:
YANG Yuling, GUO Xinliang, CUI Zhaolun, et al. Determination of H2S in SF6 Decomposition Products by Ultraviolet Absorption Spectrometry[J]. 2018, 44(8): 2573-2579.DOI:
Determination of H2S in SF6 Decomposition Products by Ultraviolet Absorption Spectrometry
decomposition products plays an important role in assessment of the insulation state in SF
6
insulated electrical equipment. H
2
S can be detected by ultraviolet absorption spectrometry for its absorption in the band of 190
2
30 nm. We set up an ultraviolet detection platform for the determination of H
2
S. However
the sensitivity of H
2
S detection was low because the absorption spectra were easy to be interfered by spectral scatting and high-frequency noise. Therefore
ultraviolet difference algorithm and wavelet function were used for volu
me fraction inversion to obtain the relationship between spectral data and gas volume fraction. The research results show that there is a good linear relationship between the frequency domain information obtained by spectral data extraction and the concentration
the method shows good linearity(R2=0.999 9) and the volume fraction limit of the detection is 0.590×10
-6
. The obtained inversion expression was used for the actual data detection
and a good detection effect was obtained. The method is of good detection repeatability and high sensitivity
and it can be integrated into portable testing equipment
which is suitable for on-line detection of trace H