Research on Structural Parts Loop Current Caused by Current of Voltage Regulation Leads of ±800 kV Converter Transformer
|更新时间:2025-12-08
|
Research on Structural Parts Loop Current Caused by Current of Voltage Regulation Leads of ±800 kV Converter Transformer
Vol. 44, Issue 7, Pages: 2424-2432(2018)
作者机构:
1. 山东电力设备有限公司
2. 山东输变电设备有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 July 2018,
Published:2018
稿件说明:
移动端阅览
ZHOU Xuntong, XU Jianwen, FENG Zhengren, et al. Research on Structural Parts Loop Current Caused by Current of Voltage Regulation Leads of ±800 kV Converter Transformer[J]. 2018, 44(7): 2424-2432.
DOI:
ZHOU Xuntong, XU Jianwen, FENG Zhengren, et al. Research on Structural Parts Loop Current Caused by Current of Voltage Regulation Leads of ±800 kV Converter Transformer[J]. 2018, 44(7): 2424-2432.DOI:
Research on Structural Parts Loop Current Caused by Current of Voltage Regulation Leads of ±800 kV Converter Transformer
Magnetic flux caused by high current in voltage regulation leads of large capacity converter transformer will generate loop current in the closed loop of the structural parts. If the loop current is too high
overheat will be caused in the structural parts
which will affect the safe operation of converter transformer. Consequently
we analyzed the cause of theloop current
and introduced countermeasures to prevent the loop current. Taking a ±800 kV converter transformer as a research subject
we theoretically analyed and calculated the loop current;meanwhile
we numerically simulated and calculated the loop current by establishing a complete leakage magnetic model of converter transformer. During the temperature-rise test of converter transformer
loop current was measured by an optical fiber current sensor. According to the test results
the accuracy and feasibility of theoretical analysis and numerical simulation were verified. The research method adopted in this paper can be used to calculate the loop current of structural parts of converter transformer and high-current devices in actual projects
which has a guiding significance for the design and safe operation of converter transformer and high-current devices.