Effectiveness of High-speed Airflow Arc-extinguishing Anti-thunder Gap to DC Arc-extinguishing
|更新时间:2025-12-08
|
Effectiveness of High-speed Airflow Arc-extinguishing Anti-thunder Gap to DC Arc-extinguishing
Vol. 44, Issue 8, Pages: 2472-2478(2018)
作者机构:
广西大学电气工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2018,
Published:2018
稿件说明:
移动端阅览
WANG Jufeng, ZHANG Huayi, LI Zijian, et al. Effectiveness of High-speed Airflow Arc-extinguishing Anti-thunder Gap to DC Arc-extinguishing[J]. 2018, 44(8): 2472-2478.
DOI:
WANG Jufeng, ZHANG Huayi, LI Zijian, et al. Effectiveness of High-speed Airflow Arc-extinguishing Anti-thunder Gap to DC Arc-extinguishing[J]. 2018, 44(8): 2472-2478.DOI:
Effectiveness of High-speed Airflow Arc-extinguishing Anti-thunder Gap to DC Arc-extinguishing
摘要
为解决雷击闪络造成的直流输电线路跳闸这一难题
建立了高速气流的速度冲击模型
分析了直流电弧运动的受力情况
并推导出直流电弧熄灭的条件;然后在建模分析的基础上
利用FLUNET软件仿真分析了在理想状态下高速气流熄灭直流弧的过程
并在高压试验室的条件下进行了灭弧试验。研究结果表明:仿真的灭弧时间为1.2 ms
而试验得出的灭弧时间为1.7 ms;由于仿真不能模拟真实的熄弧条件
因此仿真和试验得出的熄弧时间存在0.5 ms的误差
但都小于继电保护的动作时间。研究结果验证了高速气流灭弧防雷间隙熄灭直流电弧的有效性。
Abstract
In order to solve the problem of lightning flashover caused by DC transmission line trip
we established a high-speed airflow velocity shock model
analyzed the force situation of DC arc motion
and derived the extinguishing conditions of DC arc Moreover
by analying the model and using the FLUNET software
we simulated and analyzed the arc-extinguishing process in high speed flow under ideal conditions
and conducted arc-extinguishing tests in high voltage laboratory conditions. The research results show that the extinguishing time of simulation is 1.2 ms
while the extinguishing time of test is 1.7 ms. Because the arc simulation can not simulate the real conditions
there is a 0.5 ms error between the arc extinguishing time obtained by simulation and test
but both of them are less than the action time of relay protection. The results verify the effectiveness of high-speed airflow arc-extinguishing anti-thunder gap and DC arc extinguishing.
Arc-extinguishing Test on Multiple Fracture Arc-extinguishing Lightning Protection Gap with Explosion Airflow
Research on Arc-extinguishing Effectiveness of Arc-extinguishing Lightning Protection Gap Under the Action of High-speed Airflow
Research on Airflow Field Simulation and Arcing Test of Arc-extinguishing Lightning Protection Gap Under Strong Airflow
Statistical Method of Lightning Current Amplitude Distribution Along Transmission Line Corridor
Analysis on the Characteristics of Short-tail Voltage Wave of Insulator on the Double-circuit Transmission Line in Back Flashover and Design of the Experiment Circuit
Related Author
CUI Guangzhao
YAN Peng
QIU Hongbo
YAO Lina
WANG Jufeng
LI Guodong
DONG Lufei
WU Dong
Related Institution
College of Electricial and Information Engineering, Zhengzhou University of Light Industry
Economic Research Institute,State Grid Henan Electric Power Company
China Guodian Ledong Power Generation Co., Ltd.
School of Electrical Engineering, Guangxi University