Shake Table Test on UHV Standardization Lightning Arrester Installed with Shear-type Lead Dampers
|更新时间:2025-12-08
|
Shake Table Test on UHV Standardization Lightning Arrester Installed with Shear-type Lead Dampers
Vol. 44, Issue 8, Pages: 2595-2602(2018)
作者机构:
1. 中国电力科学研究院有限公司
2. 国家电网公司交流建设部
3. 国家电网公司交流建设分公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2018,
Published:2018
稿件说明:
移动端阅览
LIU Zhenlin, CHENG Yongfeng, LU Zhicheng, et al. Shake Table Test on UHV Standardization Lightning Arrester Installed with Shear-type Lead Dampers[J]. 2018, 44(8): 2595-2602.
DOI:
LIU Zhenlin, CHENG Yongfeng, LU Zhicheng, et al. Shake Table Test on UHV Standardization Lightning Arrester Installed with Shear-type Lead Dampers[J]. 2018, 44(8): 2595-2602.DOI:
Shake Table Test on UHV Standardization Lightning Arrester Installed with Shear-type Lead Dampers
In order to improve the seismic safety of ultra high voltage(UHV) porcelain arrester. First
we proposed a structural design scheme of standard porcelain bushing for UHV lightning arrester based on the method of structural seismic optimization
thus the seismic safety factor was increased from original 1.68 in the 0.2 g(g=9.81 m/s
2
) horizontal seismic acceleration test to 1.73 of the new structure in the 0.3 g horizontal seismic acceleration test. Second
we simulated and analyzed the shock absorption of the UHV standardization lightning arrester with shear-type lead damper performance parameters. Last
we conducted the earthquake simulation shaking table tests of the UHV porcelain bushing with the shear-type lead dampers
whose mod
el was got from the results of simulation analysis. Compared with non-damping in the white noise test structure
fundamental frequency of the damping structure were reduced by 2.76%
4
.15%
and the seismic safety coefficients were 2.15 and 1.86
respectively
in the horizontal seismic acceleration 0.4 g and 0.5 g tests. The test results show that the method of structural optimization and shock absorption design can be used to improve the seismic performance of UHV lightning arrester
and installation of the shear-type lead dampers has hardly influences on the overall stiffness of the electrical equipment. The research results can provide references for seismic design and test of substation electrical equipment.