Analysis of Multiple Sulfides in Transformer Oil and Experimental Study on Mercaptan Corrosion Mechanism Based on Gas Chromatography-Sulfur Chemilecminescence Detection
|更新时间:2025-12-08
|
Analysis of Multiple Sulfides in Transformer Oil and Experimental Study on Mercaptan Corrosion Mechanism Based on Gas Chromatography-Sulfur Chemilecminescence Detection
Vol. 44, Issue 8, Pages: 2565-2572(2018)
作者机构:
1. 国网福建省电力有限公司电力科学研究院
2. 华北电力大学电气与电子工程学院
3. 国网湖北省电力有限公司恩施供电公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2018,
Published:2018
稿件说明:
移动端阅览
LIAN Hongsong, LI Fangqing, CONG Haoxi, et al. Analysis of Multiple Sulfides in Transformer Oil and Experimental Study on Mercaptan Corrosion Mechanism Based on Gas Chromatography-Sulfur Chemilecminescence Detection[J]. 2018, 44(8): 2565-2572.
DOI:
LIAN Hongsong, LI Fangqing, CONG Haoxi, et al. Analysis of Multiple Sulfides in Transformer Oil and Experimental Study on Mercaptan Corrosion Mechanism Based on Gas Chromatography-Sulfur Chemilecminescence Detection[J]. 2018, 44(8): 2565-2572.DOI:
Analysis of Multiple Sulfides in Transformer Oil and Experimental Study on Mercaptan Corrosion Mechanism Based on Gas Chromatography-Sulfur Chemilecminescence Detection
To quantitatively analyze the corrosive sulfur in transformer oil
we put forward a test methodology by gas chromatograph and sulfur chemiluminescence detection. Sulfur compounds were firstly qualitatively analyzed according to their retention time
based on which the compounds were quantified accordingly with an external calibration scheme. The preferable test conditions
including carrier gas flow rate
initial oven temperature and heating procedure for both qualitative and quantitative analysis of multiple sulfides in the transformer oil
were elucidated and finalized by comparative studies. Moreover
we analzyed the
oil samples with sulfides varying from 1×10
-6
mol/L to 5×10
-3
mol/L
and studied the reaction mechanism between different mercaptans in the transformer oil and the copper. The measured results indicate that the sulfur contents have a linear relationship with the gas chromatograph peak area
and the relative standard deviation well satisfies the specified requirements of precise quantitative and qualitative analyses. The reaction process with one kind of mercaptan during transformer oil aging may only generate corresponding disulfide
while multiple mercaptans interaction can bring about crosslinking reactions
and cause new thioether apart from corresponding disulfides. The test methodology and conditions by gas chromatograph and sulfur chemiluminescence detection were established to analyze the multiple sulfide in transformer oil
and a new mechanism of mercaptan-copper reaction was put forward. The above method can provide a useful reference for the quantitative analysis of multiple sulfide.