Influence of Unbalanced Current in 3-core Power Cable on Temperature Distribution
|更新时间:2025-12-08
|
Influence of Unbalanced Current in 3-core Power Cable on Temperature Distribution
Vol. 44, Issue 8, Pages: 2704-2709(2018)
作者机构:
1. 国网湖北省电力公司电力科学研究院
2. 国家电网公司高压电气设备现场试验技术重点实验室
3. 西安交通大学电力设备电气绝缘国家重点实验室
4. 国网湖北省电力公司咸宁供电公司
5. 国网湖北省电力公司武汉供电公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 August 2018,
Published:2018
稿件说明:
移动端阅览
RUAN Ling, ZHAO Aixuan, DENG Dan, et al. Influence of Unbalanced Current in 3-core Power Cable on Temperature Distribution[J]. 2018, 44(8): 2704-2709.
DOI:
RUAN Ling, ZHAO Aixuan, DENG Dan, et al. Influence of Unbalanced Current in 3-core Power Cable on Temperature Distribution[J]. 2018, 44(8): 2704-2709.DOI:
Influence of Unbalanced Current in 3-core Power Cable on Temperature Distribution
When 3-core distribution power cable is in service
unbalanced current in 3-phase usually occurs due to the different demands of consumers load in different phases. As a result
it is necessary to determine the cable temperature rise under unbalanced current. Only balanced conditions of 3-phase current are considered in IEC 60287 and the thermal circuit method is too difficult to calculate temperature rise. Therefore
we applied a finite element method to build a numerical model for cables’ thermal field. Using the cable thermal field model
we set different unbalanced degrees in phase-A and calculated the greatest load current of phases-B and phases-C by dichotomy. According to the results
if the further unbalanced degree deviates from 0 value
the total current of cable transmitting under 90 ℃ is less. Besides
the total loss of cable is smallest when the unbalanced degree is 0.6. Distribution administrator can make use of different unbalanced degrees to decrease the line loss rate and increase the cable utilization ratio.