In order to reduce current in metal sheaths of crosslinked polyethylene(XLPE) cables
and to increase the service life and ampacity of cables
we analyzed the effect of mixed arrangement on current in metal sheaths of two-circuit arranged XLPE cables. Firstly
on the basis of the theory of electromagnetism
a process of calculation of current in metal sheaths of two-circuit arranged XLPE cables was deduced. Secondly
the value of current in sheaths of 220 kV single-core cables
which were laid in both horizontal and right angle form
was calculated by using a self-made program. The research results show that the maximum circulating current value of mixed arranged cables has reached 14.4% of load current when the cables are segmented evenly; under the segmentation of 400 m-500 m-600 m
the current value may be 24.2% of load current which is beyond the allowable range. In addition
the circulating currents in single-circuit cables is about 30% lower than that in double-circuit cables under the same laying conditions. In order to reduce the current in sheaths
Effects of Different Multi-loop Laying Ways on Circulating Current of Power Cable
Coupling Rule Between Lightning Electromagnetic Field and Twisted Pair Network
Experimental Study on Energy Coupling From Lightning to Wind Turbines Based on Artificial Triggered Lightning
Review of DC Microgrids Grounding and Study on Protection Methods Based on Control and Protection Cooperation
PDC Branch Parameter Characteristics of Water Tree Aged Cables Based on the Microstructural Characteristics of Water Trees
Related Author
CAI Ye
TANG Yiqin
ZHANG Chi
SUN Yunlian
ZOU Hongliang
WANG Xiaojia
WAN Haojiang
WANG Hao
Related Institution
School of Electrical Engineering, Wuhan University
Taizhou Power Supply Company, State Grid Zhejiang Electric Power Company
Research Institute of Electrostatic and Electromagnetic Protection, Mechanical Engineering College
China Aerodynamics Research and Development Center
Collaborative Innovation Center on Forecast and Evaluation of Meteorological Disasters (CIC-FEMD)/Key Laboratory for Aerosol-Cloud–Precipitation of China Meteorological Administration, Nanjing University of Information Science and Technology