Current in Secondary Cable Shielding Coupling to Secondary Ports in Substation
|更新时间:2025-12-08
|
Current in Secondary Cable Shielding Coupling to Secondary Ports in Substation
Vol. 44, Issue 11, Pages: 3672-3680(2018)
作者机构:
1. 清华大学电机系电力系统及发电设备控制与仿真国家重点实验室
2. 中国电力科学研究院有限公司电网环境保护国家重点实验室
3. 中国电力科学研究院有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:22 November 2018,
Published:2018
稿件说明:
移动端阅览
LIU Weidong, ZHAO Jun, CAI Yuanji, et al. Current in Secondary Cable Shielding Coupling to Secondary Ports in Substation[J]. 2018, 44(11): 3672-3680.
DOI:
LIU Weidong, ZHAO Jun, CAI Yuanji, et al. Current in Secondary Cable Shielding Coupling to Secondary Ports in Substation[J]. 2018, 44(11): 3672-3680.DOI:
Current in Secondary Cable Shielding Coupling to Secondary Ports in Substation
摘要
短时电磁暂态作用下
变电站接地体间会产生相对电位差
使二次电缆屏蔽层中流过电流并耦合至二次设备端口
从而造成运行故障甚至设备损坏。鉴于此
通过模拟试验研究获取了二次电缆屏蔽层电流对二次端口的耦合特性
并分析了耦合机理。首先
搭建了模拟开关操作、短路故障、雷击等电磁暂态作用下
电缆屏蔽层电流对端口耦合的试验平台
并开展了试验测量。试验结果表明:当二次电缆的首端和末端接有相同的元件时
各类电磁暂态作用下
首端和末端耦合的端口电压均波形相同
极性相反;双芯电缆的端口电压只有共模电压
没有差模电压。然后
建立了电缆的集总参数等效电路
通过电路分析表明
端口的骚扰电压水平与电缆屏蔽层电流通过屏蔽层电阻产生的压降相当。研究结果还表明
二次端口的耦合系数随频率的上升而降低
耦合阻抗与频率无关
其值接近电缆屏蔽层的电阻值。这些结果为进一步研究二次端口的电磁骚扰防护奠定了基础。
Abstract
Electromagnetic transient will induce a relative potential difference between earthing conductors and current in secondary cable shielding in substation. The current can couple to the secondary ports through control cables
which may cause operation failure even damage of secondary equipment. Consequently
we obtained the characteristics of the voltage and current coupled to the secondary ports through the experimental simulation
and analyzed the coupling mechanism. First
we employed established test platforms for simulating switching
short circuit and lightning transients to carry out numeral experiments. The experimental results indicate that the voltage waveforms at both terminal ports have the same profile but the opposite polarity
under the condition of the same component at the terminals for all kinds of transients. Then
only common-mode voltage with no differential-mode voltage exists for the twin core cable. Based on the results
an equivalent circuit of secondary cable was proposed. It is revealed that the current in the cable shielding layer will induce the resistance voltage drop
i.e. the voltage at the secondary port. The results also show that the coupling coefficient decreases with the increase of the frequency
and the coupling impedance
which is independent of frequency
is close to the resistance of the cable shielding layer. All these results will be helpful to further research on the electromagnetic protection of the secondary ports.