Measurement of Space Crossing Transmission Line Based on Binocular Ranging
|更新时间:2025-12-08
|
Measurement of Space Crossing Transmission Line Based on Binocular Ranging
Vol. 44, Issue 11, Pages: 3657-3663(2018)
作者机构:
太原理工大学物理与光电工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:22 November 2018,
Published:2018
稿件说明:
移动端阅览
SUN Shengnan, Lü Yuxiang, WANG Shuai, et al. Measurement of Space Crossing Transmission Line Based on Binocular Ranging[J]. 2018, 44(11): 3657-3663.
DOI:
SUN Shengnan, Lü Yuxiang, WANG Shuai, et al. Measurement of Space Crossing Transmission Line Based on Binocular Ranging[J]. 2018, 44(11): 3657-3663.DOI:
Measurement of Space Crossing Transmission Line Based on Binocular Ranging
摘要
高压输电线间距过小时容易出现相间闪络和短路等故障
为预防此类故障带来的危害
提出了基于双目测距的输电线交叉跨越测量方法。该方法基于改进的链码算法
设计了一种输电线自动检测算法
以提取输电线的像素坐标;依据双目测距原理
建立了输电线交叉跨越几何测量模型
计算了输电线间距。最后将该方法应用于对山西阳泉2条输电线的现场测量中。实际测量结果表明
该方法可以有效地对待测线路进行检测、拟合与合并
能够准确地获取待测线路的像素坐标;在几何测量模型中
待测的2条线路无论是平行
还是交叉跨越
均可被准确测量
实现了自动检测与无接触测量。与全站仪测量结果相比
新方法的最大测量误差<2%
证明新方法准确有效
满足实际测量要求。
Abstract
Excessively short distance between high voltage transmission lines will lead to serious faults such as flashover and short circuit. In order to prevent the danger caused by such faults
we put forward a measurement method of space across transmission lines based on binocular ranging. The method is based on the improved chain code algorithm
and the automatic detection algorithm of transmission line is designed to extract the pixel coordinates of transmission line; according to the binocular ranging principle
a geometric measurement model of the space crossed transmission line was built to calculate the transmission line spacing. Finally
the method was applied to the on-site measurement of 2 transmission lines in Shanxi Yangquan. The actual measurement results show that the method can effectively detect
fit and combine the lines to be measured. In the geometric measurement model
the transmission line spacing can be accurately measured both in parallel or space crossing transmission line
then automatic detection and non-contact measurement can be realized by this method. Compared with the measurement results of the electronic total station
the maximum measurement error of the new method is less than 2%
which verifies the method is accurate and effective