Electro-thermal Field Simulation and Insulation Accident Analysis of High Voltage AC Disc Insulator
|更新时间:2025-12-08
|
Electro-thermal Field Simulation and Insulation Accident Analysis of High Voltage AC Disc Insulator
Vol. 44, Issue 11, Pages: 3553-3560(2018)
作者机构:
1. 国网重庆市电力公司电力科学研究院
2. 西安交通大学电力设备电气绝缘国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:22 November 2018,
Published:2018
稿件说明:
移动端阅览
ZHANG Shiling, ZHANG Siyu, WANG Haoran, et al. Electro-thermal Field Simulation and Insulation Accident Analysis of High Voltage AC Disc Insulator[J]. 2018, 44(11): 3553-3560.
DOI:
ZHANG Shiling, ZHANG Siyu, WANG Haoran, et al. Electro-thermal Field Simulation and Insulation Accident Analysis of High Voltage AC Disc Insulator[J]. 2018, 44(11): 3553-3560.DOI:
Electro-thermal Field Simulation and Insulation Accident Analysis of High Voltage AC Disc Insulator
Disc insulator is widely used in gas insulated station(GIS) equipment
which is an important part of the electrical isolation between central conductors and a grounding flange. We analyzed the insulation performances of materials used in the disc insulator. The heating curve of the disc insulator was obtained by using the theoretical model
and an insulation accident was analyzed using this curve. The electric and thermal field distribution of the disc insulator was obtained through the electro-thermal coupling analysis process
and the relationship between the hot-spot temperature and the current load was calculated. The research results show that the insulating properties of the spacer material have significant nonlinear relationship with temperature. The eddy current field and harmonic field analysis method by finite element method(FEM) can effectively calculate the heat of center conductors and a spacer under 50 Hz condition. The maximum electric field strength locates at the interface of center conductors and a spacer with value of 6.033 MV/m
and the hot spot is near center conductors of a spacer with value of 82 ℃. When the load is higher than 1.5 times of the rated value
the sudden rise of temperature will appear which is called thermal collapse phenomenon. Therefore
the thermal and electric field coupling calculation process provides a way to check the performance of the design scheme of the disc insulator
and can also provide a theoretical guidance for the field maintenance and accident analysis of disc insulators.