Fault Line Selection Method Based on Optimized Bistable Denoising for Non-solid-earthed Network
|更新时间:2025-12-08
|
Fault Line Selection Method Based on Optimized Bistable Denoising for Non-solid-earthed Network
Vol. 44, Issue 11, Pages: 3483-3492(2018)
作者机构:
1. 上海电力学院自动化工程学院
2. 国网浙江省电力有限公司温州供电公司
3. 西安交通大学电气工程学院
4. 河南理工大学电气工程与自动化学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:22 November 2018,
Published:2018
稿件说明:
移动端阅览
CHENG Qiming, GAO Jie, WANG Xiaowei, et al. Fault Line Selection Method Based on Optimized Bistable Denoising for Non-solid-earthed Network[J]. 2018, 44(11): 3483-3492.
DOI:
CHENG Qiming, GAO Jie, WANG Xiaowei, et al. Fault Line Selection Method Based on Optimized Bistable Denoising for Non-solid-earthed Network[J]. 2018, 44(11): 3483-3492.DOI:
Fault Line Selection Method Based on Optimized Bistable Denoising for Non-solid-earthed Network
To solve the problems that it is difficult to extract fault features in strong noise background and fault conditions randomly occur when signal phase ground faults occur in non-solid-earthed network
we proposed a fault line selection method based on optimized bistable denoising for non-solid-earthed network. Firstly
based on the analysis of the influence of noise on transient zero-sequence current(TZSC)
the genetic algorithm and bistable system were applied in the denoising of TZSC. Secondly
according to the peak value of TZSC
the fault situation was divided into three mode: strong fault mode
medium fault mode
and weak fault mode
and the three optimized bistable systems were obtained. Thirdly
the TZSC for each line was denoised by these three bistable systems
and the transient characteristic zero-sequence current(TCZC) was acquired by the principle of peak current. Finally
the polarity parameters for each lines were determined by the TCZC
and a fault line selection criterion based on the polarity parameter and polarity standard deviation was proposed. The simulation results show that
the proposed method can select fault line exactly in different fault environments including different fault resistances
fault angle
ault distance
and so on
even in the strong noise background of which the signal-to-noise ratio is-1 d B
the proposed method can filter the noise
when the fault is not busbar fault
it can make the polarity standard deviation bigger than 0.01 and the polarity parameter of faulty line is smaller than healthy line; when the fault is busbar fault
it can make the polarity standard deviation smaller than 0.01. The research results verified the effectiveness of the proposed fault line selection method.