Partial Discharge Characteristics of Cavity Defect in Nomex Insulation for Dry Type Transformer
|更新时间:2025-12-08
|
Partial Discharge Characteristics of Cavity Defect in Nomex Insulation for Dry Type Transformer
Vol. 44, Issue 12, Pages: 4071-4082(2018)
作者机构:
1. 太原理工大学煤矿电气设备与智能控制山西重点实验室
2. 国网忻州供电公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 December 2018,
Published:2018
稿件说明:
移动端阅览
SONG Jiancheng, ZHU Jingjing, TIAN Muqin, et al. Partial Discharge Characteristics of Cavity Defect in Nomex Insulation for Dry Type Transformer[J]. 2018, 44(12): 4071-4082.
DOI:
SONG Jiancheng, ZHU Jingjing, TIAN Muqin, et al. Partial Discharge Characteristics of Cavity Defect in Nomex Insulation for Dry Type Transformer[J]. 2018, 44(12): 4071-4082.DOI:
Partial Discharge Characteristics of Cavity Defect in Nomex Insulation for Dry Type Transformer
In order to investigate the characteristics of the partial discharge(PD) defects on the Nomex paper used for mining dry-type transformer insulation with cavity
we theoretically analyzed the relationship between the electric field strength or partial discharge inception voltage of Nomex insulation and the type and dimension of cavity. The electric field and space charge distribution of cavity within Nomex insulation were simulated before and after partial discharge occurred in COMSOL Multiphysics. Then the model with artificial cavity in Nomex insulation was prepared. Based on this model
continuous tests using the constant voltage method were developed. The partial discharge characteristics were measured in the laboratory. Finally
the cavity discharge mechanism was analyzed. The results reveal that the electric field strength distribution of cavity in the Nomex
as well as the inception voltage of partial discharge
depends on the type and dimension of cavity. Moreover
partial discharge in the cavity is closely related to the distribution of both the electric field and the space charge. In addition
It is also concluded that the accumulative total discharge and average discharge energy per second in a stable trend and followed consistent rules are best indicators that are able to characterize the severity of the defects. This results has been applied to the pattern recognition and insulation life assessment of insulation for a 10 kV dry-type transformer in a coal mine and it has great application significance.