Contamination Characteristic of Porcelain Long Rod Insulator in Condition of Heavy Pollution and Brief Rain
|更新时间:2025-12-08
|
Contamination Characteristic of Porcelain Long Rod Insulator in Condition of Heavy Pollution and Brief Rain
Vol. 44, Issue 12, Pages: 3951-3957(2018)
作者机构:
1. 湖北工业大学电气与电子工程学院
2. 武汉大学电气工程学院
3. 江苏省电力公司检修分公司
4. 江苏省电力公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 December 2018,
Published:2018
稿件说明:
移动端阅览
YANG Shuai, ZHENG Qiuwei, CUI Yandong, et al. Contamination Characteristic of Porcelain Long Rod Insulator in Condition of Heavy Pollution and Brief Rain[J]. 2018, 44(12): 3951-3957.
DOI:
YANG Shuai, ZHENG Qiuwei, CUI Yandong, et al. Contamination Characteristic of Porcelain Long Rod Insulator in Condition of Heavy Pollution and Brief Rain[J]. 2018, 44(12): 3951-3957.DOI:
Contamination Characteristic of Porcelain Long Rod Insulator in Condition of Heavy Pollution and Brief Rain
摘要
长棒形瓷绝缘子在重污秽、少降雨环境下积污严重
存在污闪隐患。为此选取长棒形瓷绝缘子用量较大、年平均降雨较少的徐州市
在岱姚5667线d级污区悬挂长棒形瓷绝缘子和盘型瓷绝缘子
对比少雨积污期内的自然积污差异;采用人工积污试验和积污仿真模型
研究长棒形瓷绝缘子的积污特性。结果表明:2016年2—4月的自然少雨环境中
长棒形瓷绝缘子各月平均积污量都大于盘型瓷绝缘子
两者的等值盐密比约为3.4:1;风洞模拟的积污环境下
长棒形瓷绝缘子LP75、LP85的等值盐密、灰密均大于盘型瓷绝缘
芯棒直径较小的长棒形瓷绝缘子积污更多;仿真结果表明
受开放伞型结构的影响
污秽颗粒在气流作用下更易与长棒形瓷绝缘子表面发生碰撞。在重污少雨环境下
长棒形瓷绝缘子自洁性难以体现
应及时清扫。
Abstract
Heavy contaminant accumulates on the insulator surface of porcelain long rod insulator in condition of heavy pollution and brief rain
which poses a flashover hazard to the power system. Consequently
taking Xuzhou city
which is in semi-humid area and where a large amount of porcelain long rod insulators are used and porcelain long rod insulators and disk type porcelain insulators are hung up on the Daiyao 5667 transmission line for several months
as an investigation object
we compared the contaminant difference between these two insulators. The contamination characteristics of porcelain long rod insulator were analyzed by wind tunnel artificial contamination tests and a simulation model. According to the measurement of insulators hung up
more contaminants accumulate on the surface of porcelain long rod insulator than on the disk type porcelain insulator in condition of brief rain from Feb. to Apr. in 2016. The ESDD ratio of porcelain long rod insulator to disk type porcelain insulator is 3.4:1. The ESDD and NSDD are both greater than that obtained on porcelain long rod insulator based on the wind tunnel artificial contamination tests. Furthermore
more contaminants accumulates on the porcelain long rod insulator with a smaller rod diameter. Due to the open umbrella structure of porcelain long rod insulator
there is larger area ratio which is stroke by the contamination particulate. Porcelain long rod insulator in transmission line should be cleaned in time especially in the heavy pollution and brief rain area.