Influence of Beating Degree on Properties of Cellulose Insulation Paper
|更新时间:2025-12-08
|
Influence of Beating Degree on Properties of Cellulose Insulation Paper
Vol. 44, Issue 12, Pages: 3777-3783(2018)
作者机构:
1. 重庆大学输配电装备及系统安全与新技术国家重点实验室
2. 国网江苏省电力有限公司苏州供电分公司
3. 湖南广信科技股份有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 December 2018,
Published:2018
稿件说明:
移动端阅览
LIAO Ruijin, YAN Shuiqiang, YANG Lijun, et al. Influence of Beating Degree on Properties of Cellulose Insulation Paper[J]. 2018, 44(12): 3777-3783.
DOI:
LIAO Ruijin, YAN Shuiqiang, YANG Lijun, et al. Influence of Beating Degree on Properties of Cellulose Insulation Paper[J]. 2018, 44(12): 3777-3783.DOI:
Influence of Beating Degree on Properties of Cellulose Insulation Paper
Beating degree of cellulose insulation paper is a comprehensive reflection of the fiber being cut
swelled and fibrillated
and it has a direct impact on insulation performance of oil-paper composite insulation in power transformers. In order to study the influence of beating degree on the insulation properties of insulation paper
paper with five beating degrees was prepared and immersed with 25# mineral oil
then the mechanical properties
breakdown strength
and dielectric properties of paper were tested. The microstructure of fiber morphology was observed by SEM and the effect of beating degree on the mechanical strength was researched. By using the tape model of oil impregnated paper
the influence mechanisms of beating degree on electrical insulation properties were analyzed. The research results show that
as the beating degree increases
the fibers gradually become shorter and thinner
and the connection between fibers get enhanced
wheras the fibers are severely damaged while the beating degree is too high. Therefore
the mechanical strength and electrical strength present a trend of rise firstly and then fall with the increase of beating degree. In addition
the energy level inside paper decreases firstly and then increases
and the trends of permittivity and dielectric loss are as the same as energy level. In summary
it is considered that paper with 85 o SR beating degree has better insulation performance compared with other beating degrees.