Lightning Impulse Discharge Performance of Switchgear Air Gaps at Low Air Pressure
|更新时间:2025-12-08
|
Lightning Impulse Discharge Performance of Switchgear Air Gaps at Low Air Pressure
Vol. 45, Issue 3, Pages: 914-921(2019)
作者机构:
1. 重庆大学输配电装备及系统安全与新技术国家重点实验室
2. 重庆广仁铁塔制造有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:14 March 2019,
Published:2019
稿件说明:
移动端阅览
ZHANG Zhijin, WEI Donghong, JIANG Xingliang, et al. Lightning Impulse Discharge Performance of Switchgear Air Gaps at Low Air Pressure[J]. 2019, 45(3): 914-921.
DOI:
ZHANG Zhijin, WEI Donghong, JIANG Xingliang, et al. Lightning Impulse Discharge Performance of Switchgear Air Gaps at Low Air Pressure[J]. 2019, 45(3): 914-921.DOI:
Lightning Impulse Discharge Performance of Switchgear Air Gaps at Low Air Pressure
The electric safety distance of a switch cabinet with air as insulation medium is obviously affected by altitude
electrode shape
and so on. But there is no relative standard for the selection of air gap of switch cabinet at low pressures.To study the lightning impulse discharge performance of switchgear air gaps under high altitude condition
4 types of air gap existing in 40.5 kV switchgear and typical rod-plane air gap were chosen as research subjects
and the effects of electrode shape
air pressure p
humidity h and air gap distance d on discharge characteristic were investigated. Tests results show that the discharge characteristic difference between rod-plane air gap and switchgear air gaps is noticeable. The lightning discharge voltage U50 can be expressed as U50=U50
0(p/p0+ch)n
in which U50
0 is discharge voltage at the sea level altitude p0. The variation of humidity will cause dispersion of U50 and the relationship between U50 and d(<400 mm)is non-linear. The research results can provide guidance for the design
selection and installation of switchgear in high altitude areas.