Influence of Integrated Grounding System for High-speed Railway on the Grounding Impedance Measurement of Traction Substation
|更新时间:2025-12-08
|
Influence of Integrated Grounding System for High-speed Railway on the Grounding Impedance Measurement of Traction Substation
Vol. 45, Issue 3, Pages: 723-729(2019)
作者机构:
南方电网科学研究院有限责任公司直流输电技术国家重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:14 March 2019,
Published:2019
稿件说明:
移动端阅览
ZHANG Yi, CAI Hansheng, JIA Lei, et al. Influence of Integrated Grounding System for High-speed Railway on the Grounding Impedance Measurement of Traction Substation[J]. 2019, 45(3): 723-729.
DOI:
ZHANG Yi, CAI Hansheng, JIA Lei, et al. Influence of Integrated Grounding System for High-speed Railway on the Grounding Impedance Measurement of Traction Substation[J]. 2019, 45(3): 723-729.DOI:
Influence of Integrated Grounding System for High-speed Railway on the Grounding Impedance Measurement of Traction Substation
The grounding grid of traction substation is within the influence scope of the integrated grounding system for high-speed railway
and the measurement of its grounding impedance is bound to be influenced by the integrated grounding system for high-speed railway
therefore
it can not simply copy the grounding impedance measurement method of power system grounding device. Based on the CDEGS software
we established a calculation model of the grounding impedance of grounding grid in traction substation in the existence of integrated grounding system for high-speed railway
and analyzed the influence of the integrated grounding system for high-speed railway on the ground potential rise distribution of traction substation grounding grid under a homogeneous soil resistivity. Thereby
the simulation model of grounding impedance measurement of grounding grid in a traction substation was established in the presence of integrated grounding system for high-speed railway. We also analyzed the accuracy of measuring the grounding impedance of traction substation by an angle measurement method under different electrode arrangements and different current electrode distances
and performed the field tests. The simulation calculation and the field measurement show that the existence of integrated grounding system for high-speed railway reduces the influence scope of the grounding grid of traction substation
and seriously affects the accuracy of the angle measurement method for measuring the grounding impedance of traction substation. Reasonable arrangements of current electrode and voltage electrode can reduce the influence of integrated grounding system for high-speed railway on grounding impedance measurement of traction substation grounding grid
and a 30-degree-beyond angle method is suitable for the grounding impedance measurement of the grounding grid in traction substation in the existence of integrated grounding system for high-speed railway.
Grounding Impedance and Current Dispersed Characteristics of High-speed Railway Integrated Grounding System
Experimental Studies on Application Characteristics of Lightning Protection for Long Rod Suspension Composite Insulators for High-speed Railway Catenary
Method of Lightning Hazard Risk Evaluation for Traction Electric Network of High-speed Railway
Attracted Lightning Characteristics of High-speed Railway Catenary Based on Leader Propagation Model
Life Prediction for Protection System of Traction Substation Based on Weibull Distribution
Related Author
QI Guangfeng
SUN Jianming
ZHOU Mi
ZHANG Yi
FAN Yadong
WANG Jianguo
CHEN Kang
SHEN Haibin
Related Institution
China Railway Siyuan Survey and Design Group Co., Ltd.
School of Electrical Engineering, Wuhan University