Pollution Flashover Characteristics of Insulator Strings with Inverted T-type Arrangement
Reasonable insulator string arrangement is one of the effective ways to improve the pollution flashover voltage.At present
most of the existing references of the forms of insulator strings are mainly related to insulator string arranged in V-type and inverted V-type
but rarely related to insulator string arranged in inverted T-type. We adopted a uniform increase voltage method to test XWP-70 and other two inverted V-type insulator strings and compared with the ordinary hanging string. Through the experiments
it can be found that the flashover voltage of the inverted T-type insulator string has a power function relation to ESDD. Compared with the ordinary hanging string
the inverted T-type insulator string flashover voltage increases by 11.6%~22.3%; and with the increase in salt density
the percentage of flashover voltage improvement also increases. According to the results
the equivalent coefficient of the inverted T-type insulator string in each pollution area is calculated
and it will be convenient to select the inverted T-type insulator string’s length.