Method of Online Status Monitoring for Windings of Three-winding Transformer Based on Improved Parameter Identification
|更新时间:2025-12-08
|
Method of Online Status Monitoring for Windings of Three-winding Transformer Based on Improved Parameter Identification
Vol. 45, Issue 5, Pages: 1567-1575(2019)
作者机构:
1. 山东大学电网智能化调度与控制教育部重点实验室
2. 中国南方电网有限责任公司电力调度控制中心
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 May 2019,
Published:2019
稿件说明:
移动端阅览
CHEN Yiming, LIANG Jun, ZHANG Jingwei, et al. Method of Online Status Monitoring for Windings of Three-winding Transformer Based on Improved Parameter Identification[J]. 2019, 45(5): 1567-1575.
DOI:
CHEN Yiming, LIANG Jun, ZHANG Jingwei, et al. Method of Online Status Monitoring for Windings of Three-winding Transformer Based on Improved Parameter Identification[J]. 2019, 45(5): 1567-1575.DOI:
Method of Online Status Monitoring for Windings of Three-winding Transformer Based on Improved Parameter Identification
The electrical parameters identification is an important means to realize the winding condition monitoring of power transformers. Therefore
was proposed a method of on-line monitoring based on short-circuit reactance identification for three-winding transformer. In order to improve the accuracy of parameter identification
we investigated the relationship between different load distributions of the transformer and the condition number of the coefficient matrix.Using the condition number as a criterion
we adjusted the number of solution parameters according to different load states of the transformer. Furthermore
relying on the big data platform
we established an on-line monitoring method for transformer windings by reasonable screening data and identification scheme adaptive matching. Finally
numerical simulation was used to verify the influence of condition number on accuracy of parameter identification
while the engineering data were used to demonstrate the performance of on-line monitoring. The results show that the condition number of the coefficient matrix has an obvious influence on the accuracy of parameter identification
where the condition number is positively correlated with the error of the identification result. At the same time
the analysis of the actual engineering data by this method is consistent with the real state of the transformer. The results of this study can provide references for parameter identification and on-line status monitoring of three-winding transformer.