Simulation Analysis of Arc Characteristics on Breaking Zero Zone in High Voltage SF6 Circuit Breaker
|更新时间:2025-12-08
|
Simulation Analysis of Arc Characteristics on Breaking Zero Zone in High Voltage SF6 Circuit Breaker
Vol. 45, Issue 5, Pages: 1420-1428(2019)
作者机构:
1. 国网辽宁省电力有限公司电力科学研究院
2. 辽宁东科电力有限公司
3. 国网高电压强电流实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 May 2019,
Published:2019
稿件说明:
移动端阅览
WANG Feiming, ZHAO Yisong, SHI Kejian, et al. Simulation Analysis of Arc Characteristics on Breaking Zero Zone in High Voltage SF6 Circuit Breaker[J]. 2019, 45(5): 1420-1428.
DOI:
WANG Feiming, ZHAO Yisong, SHI Kejian, et al. Simulation Analysis of Arc Characteristics on Breaking Zero Zone in High Voltage SF6 Circuit Breaker[J]. 2019, 45(5): 1420-1428.DOI:
Simulation Analysis of Arc Characteristics on Breaking Zero Zone in High Voltage SF6 Circuit Breaker
In order to analyze the physical process between zero zone arc plasma and airflow intermolecular energy transport in the high voltage SF6 circuit breaker
and find the optimal control strategy of small current arc switching
the simulation analysis of arc characteristics on breaking zero zone is presented. The coupled field calculation physics of the breaking arc energy in the circuit breaker was established to calculate the spatial distribution of the zero zone arc plasma density and thermodynamic characteristics parameters. Using the comprehensive evaluation method of multiple physical state parameters
the effects of different breaking current
arcing time
breaking speed and other factors on the energy transport process betwe
en zero zone arc and gas flow were analyzed
the variation law and parameter range of the zero zone arc plasma physical properties were obtained. The calculation results show that there is a significant convection effect between the airflow and the arc. When the insulation break point with a temperature less than 4 000 K
a density greater than 3 kg/m
3
enthalpy value less than 1.6×107 J/kg
and a conductivity less than 800 S/m
the arc extinguishes.The research results can provide important theoretical basis for the design of the arc-extinguishing chamber of the high-voltage SF
6
circuit breaker
the selection of the mechanical characteristics of the operation
and the physical characteristics of the arc-extinguishing process.