Grid-connected Control of Microgrid with Photovoltaic and Energy Storage Systems Under Unbalanced Grid Voltage Conditions
|更新时间:2025-12-08
|
Grid-connected Control of Microgrid with Photovoltaic and Energy Storage Systems Under Unbalanced Grid Voltage Conditions
Vol. 45, Issue 6, Pages: 1879-1888(2019)
作者机构:
兰州交通大学自动化与电气工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2019,
Published:2019
稿件说明:
移动端阅览
TANG Min’an, GAO Xiaohong. Grid-connected Control of Microgrid with Photovoltaic and Energy Storage Systems Under Unbalanced Grid Voltage Conditions[J]. 2019, 45(6): 1879-1888.
DOI:
TANG Min’an, GAO Xiaohong. Grid-connected Control of Microgrid with Photovoltaic and Energy Storage Systems Under Unbalanced Grid Voltage Conditions[J]. 2019, 45(6): 1879-1888.DOI:
Grid-connected Control of Microgrid with Photovoltaic and Energy Storage Systems Under Unbalanced Grid Voltage Conditions
The photovoltaic(PV) grid-connected system with hybrid energy storage(HESS) not only effectively solves the randomness and fluctuation of traditional PV power generation
but also overcomes the contradiction between the power density and the energy density of a single energy storage system. However
the output power quality will be worse
and the overcurrent will appear on the inverter side under unbalanced grid voltage condition. This will affect the operation stability of the entire system. In order to restrain the doubling frequency pulsation of the current in the energy storage converter
and secondary pulsation in grid-connected power in order to improve the power quality; the harmonics and overcurrent problems of the grid current reference value are analyzed in the two-phase stationary coordinate system. The current-limited model predictive direct power control(MPDPC) with power compensation is proposed. The double frequency notch filter is introduced in HESS
combining with the model predictive current control
the fast-dynamic response of the system and the high-power quality are realized. The system simulation model has been built in MATLAB/Simulink and tested for different working conditions. Simulation results show that the proposed control strategy can stabilize the secondary ripple of the current in the energy storage converter
and the output power of the inverter.At the same time this can achieve the suppression of the fault overcurrent during the coordinated control of the active/reactive power
and the negative sequence current under imbalanced grid voltage.