Comparisons of Methods for Determining Corona Onset Voltage of Smooth DC Conductors
|更新时间:2025-12-08
|
Comparisons of Methods for Determining Corona Onset Voltage of Smooth DC Conductors
Vol. 45, Issue 6, Pages: 1851-1856(2019)
作者机构:
1. 华北电力大学新能源电力系统国家重点实验室
2. 国网冀北电力有限公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2019,
Published:2019
稿件说明:
移动端阅览
LI Xuebao, WANG Donglai, ZHANG Jinglan, et al. Comparisons of Methods for Determining Corona Onset Voltage of Smooth DC Conductors[J]. 2019, 45(6): 1851-1856.
DOI:
LI Xuebao, WANG Donglai, ZHANG Jinglan, et al. Comparisons of Methods for Determining Corona Onset Voltage of Smooth DC Conductors[J]. 2019, 45(6): 1851-1856.DOI:
Comparisons of Methods for Determining Corona Onset Voltage of Smooth DC Conductors
can be generated along with the corona discharge. In order to investigate the differences of corona onset voltages generated by different corona effects
a platform using the cylinder corona cage for determining the corona onset voltage was set up. The ion current densities
ionized fields
steady corona current
and ultraviolet photons from smooth conductors with different diameters were measured simultaneously in the experiments. Comparisons of the corona onset voltages from different corona effects are given through the inflexion-point method. Besides
numerical simulations for the corona onset voltage are also presented on the basis of the analytical formulas for ionized field of cylinder structure and the empirical formulas for onset electric field. The calculated results of the corona onset voltages for different conductors can match the measured ones
and the maximum error is less than 2.1%. Therefore
we proposed to use the cylinder corona cage to measure the multiple corona effects and to use the inflexion-point method to determine the corona onset voltage for the smooth conductor.