Adaptive Three-phase Reclosing Scheme of Transmission Lines Without Shunt Reactors Using Additional Capacitors
|更新时间:2025-12-08
|
Adaptive Three-phase Reclosing Scheme of Transmission Lines Without Shunt Reactors Using Additional Capacitors
Vol. 45, Issue 6, Pages: 1811-1818(2019)
作者机构:
1. 新疆大学可再生能源发电与并网技术教育部工程研究中心
2. 国网新疆电力有限公司经济技术研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2019,
Published:2019
稿件说明:
移动端阅览
XIE Chao, LI Fengting, FAN Yanfang, et al. Adaptive Three-phase Reclosing Scheme of Transmission Lines Without Shunt Reactors Using Additional Capacitors[J]. 2019, 45(6): 1811-1818.
DOI:
XIE Chao, LI Fengting, FAN Yanfang, et al. Adaptive Three-phase Reclosing Scheme of Transmission Lines Without Shunt Reactors Using Additional Capacitors[J]. 2019, 45(6): 1811-1818.DOI:
Adaptive Three-phase Reclosing Scheme of Transmission Lines Without Shunt Reactors Using Additional Capacitors
Fault and secondary strikes to power system may occur when the reclosing devices for traditional transmission lines blindly reclose without identifying fault characteristic. The existing studies of fault characteristic identification based on electric parameters cannot adapt to three-phase reclosure of transmission lines without shunt reactor because the electric parameters will damp quickly after its three-phase tripping. Therefore
we proposed an adaptive three-phase reclosing scheme of transmission lines in the absence of shunt reactors using additional capacitors. The status of transmission line was tested through the discharging(charging) current of additional capacitors installed at one end of the transmission line.The arc extinguish time and fault characteristic were determined by cycle judgment. Theoretical analysis and simulation based on PSCAD/EMTDC verify that the proposed transmission line adaptive three-phase reclosing scheme can identify the fault characteristic accurately under various kind of transmission line faults
is not influenced by transition resistance and fault location