Multi-physics Coupling Simulation and Experiment of Temperature Rise in GIS and Heat Flux Distribution Characteristics
|更新时间:2025-12-08
|
Multi-physics Coupling Simulation and Experiment of Temperature Rise in GIS and Heat Flux Distribution Characteristics
Vol. 45, Issue 7, Pages: 2322-2328(2019)
作者机构:
1. 西安交通大学电力设备电气绝缘国家重点实验室
2. 南方电网科学研究院有限责任公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 July 2019,
Published:2019
稿件说明:
移动端阅览
HOU Guobin, FU Mingli, DENG Xiaofeng, et al. Multi-physics Coupling Simulation and Experiment of Temperature Rise in GIS and Heat Flux Distribution Characteristics[J]. 2019, 45(7): 2322-2328.
DOI:
HOU Guobin, FU Mingli, DENG Xiaofeng, et al. Multi-physics Coupling Simulation and Experiment of Temperature Rise in GIS and Heat Flux Distribution Characteristics[J]. 2019, 45(7): 2322-2328.DOI:
Multi-physics Coupling Simulation and Experiment of Temperature Rise in GIS and Heat Flux Distribution Characteristics
采用三维多物理场耦合方法分析GIS的电磁场、温度场和气流场。首先利用Ansys Maxwell 3D模块计算获得GIS的欧姆损耗为1 107.8 W
将欧姆损耗作为热源导入Ansys Fluent模块进行热流耦合计算
得到温度分布和流速分布
电接触处和外壳的温升最高约为52.5K和20K;然后研究了GIS对流和辐射热通量的分布特性
并分析了不同传热方式的影响
为以后的传热分析方法奠定了基础;最后进行了温升实验
仿真与实验的最大误差为3.601 K
验证了仿真方法的正确性
进而可以为产品的优化设计提供理论依据。
Abstract
Accurate prediction of GIS temperature-rise and analysis of the heat flux distribution are very important for the design of GIS. Using the 3-D multi-physics coupling method
we established a 3-D electromagnetic-thermal-flow coupled model to analyze the electromagnetic field
temperature field and gas flow field of 126 kV three-phase-in-one-tank type GIS. Firstly
the Ohmic losses of GIS which were calculated to be 1 107.8 W by Ansys Maxwell 3 D were introduced into Ansys Fluent as heat source to calculate the temperature distribution and velocity distribution
and the highest temperature-rises of electrical contact area and shell were about 52.5 K and 20 K
respectively. Then the distribution characteristics of convection and radiation heat flux were analyzed
which lays a foundation for the future heat transfer analysis method. Finally
the temperature-rise test results were compared with the simulation results and the maximum error was 3.601 K
which verifies the correctness of the simulation results. Thereby
the multi-physics calculation of GIS can provide a theoretical basis for the optimal design of the product.
Simulation Study on the Influence of Forced Convection Heat Dissipation on Temperature Rise of Switch-gear
Pollution and Water Molecule Effects on Porcelain Post Insulator Heating
Ablation Damage and Temperature Rise of Metal Oil Tanks Struck by Direct Lightning
Numerical Simulation and Experimental Study of Heat Transfer Characteristics in Transformer Bushing
Hot Spot Temperature of Cable Joint Considering Contact Resistance
Related Author
WANG Zengbin
WANG Rui
YAO Congwei
MA Xinyou
SUN Shuai
WANG Lijun
WANG Fochi
MA Jianqiao
Related Institution
Guangdong Key Laboratory of Electric Power Equipment Reliability
Electric Power Research Institute, Guangdong Power Grid Co., Ltd.
Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense,North China Electric Power University
State Key Laboratory of Chemicals Safety, Safety Engineering Institute, China Petroleum & Chemical Corporation
Key Laboratory of Control of Power Transmission and Conversion, Ministry of Education, Department of Electrical Engineering of Shanghai Jiao Tong University