Mechanism of Incontrollable DC Voltage of Sub Modules for Cascaded STATCOM Under Higher Voltage Based on Average Modeling
|更新时间:2025-12-08
|
Mechanism of Incontrollable DC Voltage of Sub Modules for Cascaded STATCOM Under Higher Voltage Based on Average Modeling
Vol. 45, Issue 7, Pages: 2134-2140(2019)
作者机构:
1. 华中科技大学电气与电子工程学院
2. 江西省电力科学研究院
3. 浙江大学机械工程学院
4. 南昌工程学院机械与电气工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 July 2019,
Published:2019
稿件说明:
移动端阅览
ZHANG Yang, WAN Anping, YANG Xiaopin. Mechanism of Incontrollable DC Voltage of Sub Modules for Cascaded STATCOM Under Higher Voltage Based on Average Modeling[J]. 2019, 45(7): 2134-2140.
DOI:
ZHANG Yang, WAN Anping, YANG Xiaopin. Mechanism of Incontrollable DC Voltage of Sub Modules for Cascaded STATCOM Under Higher Voltage Based on Average Modeling[J]. 2019, 45(7): 2134-2140.DOI:
Mechanism of Incontrollable DC Voltage of Sub Modules for Cascaded STATCOM Under Higher Voltage Based on Average Modeling
Cascaded STATCOM under high voltage is easily balanced during heavy loads but probably out of control at empty loads. Research on the mechanism of out-of-control at empty loads is the key to solution of this problem.Consequently
we emphatically research the main contents include as follows: ①Equivalent circuit diagram of serial impedance
parallel impedance and control power consumption are simplified and drawn
respectively. ②According to the average modeling theory
the DC capacitor voltage is decomposed into the direct current component and the alternating current component
the alternating current is decomposed into the fundamental wave and the harmonic component
and the modulation degree equivalent switch function is used to list the mathematical expression of the DC voltage of the single power module. ③According to the small signal method of stability analysis
the steady-state component and the disturbance component of the DC capacitor voltage of a power module are calculated. ④In the two cases whether the DC voltage balance control is adopted or not
the DC voltage balance equation of any two power modules of the convert chain at the heavy load and the light load is deduced and calculated
and the DC voltage balance is related to the modulation de-gree
switching frequency
and other factors.(5)An improved DC voltage balance control strategy is proposed. The switching frequency is increased to improve the voltage balancing performance at empty load. In the end
simulations and tests are used to compare the results under four typical operating conditions. The results show that the voltage-sharing control strategy proposed under empty-load conditions can achieve DC capacitor voltage equalization of the power module to increase reliability of the cascaded STATCOM.