ZHANG Jinbo, WANG Lei, LIANG Shibin, et al. Influence of Mountain Topographic Slope and Stratified Conductivity Structure on Lightning Induced Voltages[J]. 2019, 45(9): 2936-2944.
DOI:
ZHANG Jinbo, WANG Lei, LIANG Shibin, et al. Influence of Mountain Topographic Slope and Stratified Conductivity Structure on Lightning Induced Voltages[J]. 2019, 45(9): 2936-2944.DOI:
Influence of Mountain Topographic Slope and Stratified Conductivity Structure on Lightning Induced Voltages
In order to investigate the influences of mountainous terrain on lightning induced voltages
a two-dimensional finite-difference time-domain(2-D FDTD) method was proposed to calculate the lightning induced voltages of overhead lines in hilly terrain. The validation of the FDTD algorithm was verified by comparing with the relevant research results abroad. The effects of the inclination angle
conductivity as well as its stratified structure on the lightning induced voltages of overhead lines were also calculated by the method proposed in this paper. The results show that
compared with the ideal flat terrain
the slope of the mountain terrain has a significant impact on the lightning overvoltage
especially in the case of limited soil conductivity
and the overvoltage amplitude increases significatly with the increase of the terrain slope; when the conductivity of surface soil is lower than the conductivity of lower-layer soil(σ1<σ2)
the induced overvoltage amplitude increases significantly as the thickness of surface soil increases; while the conductivity of surface soil is larger(σ1>σ2)
the lightning overvoltage amplitude decreases rapidly as the thickness of surface soil increases. When the thickness of surface soil exceeds 5 m
the overvoltage amplitude mainly depends on the conductivity of surface soil
and the influence of soil stratification can be neglected. The research results can provide a theoretical reference for lightning protection design of mountainous overhead transmission and distribution lines.
Calculation and Analysis of Lightning Induced Overvoltage with Stratified Ground Structure
Impact of Canceling Artificial Grounding Electrode on the Back-flashover Characteristics of UHV Double-circuit Transmission Line
Simulation Study of Lightning Induced Voltages Characteristics on Overhead Lines Over Complex Mountainous Terrain
Attachable Transient Model and Its Modular Packaging of Transformer Winding Multi-conductor Transmission Lines with External Distributed Parameter Components
Related Author
GAO Jinge
ZHANG Liang
LI Dongshuai
ZHANG Qilin
TANG Xiao
HE Junjia
SHEN Haibin
ZHAO Xiangen
Related Institution
Key Laboratory for Aerosol-Cloud-Precipitation of China Meteorological Administration, Collaborative Innovation Center on Forecast and Evaluation of Meteorological Disasters, Nanjing University of Information Science and Technology
East China Branch of Sinopec Group
College of Atmospheric Physics, Nanjing University of Information Science and Technology
Beijing Meteorological Bureau
State Key Laboratory of Advanced Electromagnetic Engineering and Technology,School of Electrical and Electronic Engineering,Huazhong University of Science and Technology