Breaking Characteristics of AC-filter Breaker for UHVDC with Hierarchical Connection to AC Grid
|更新时间:2025-12-08
|
Breaking Characteristics of AC-filter Breaker for UHVDC with Hierarchical Connection to AC Grid
Vol. 45, Issue 9, Pages: 2857-2865(2019)
作者机构:
1. 电力规划总院有限公司
2. 清华大学电机工程与应用电子技术系电力系统及发电设备控制和仿真国家重点实验室
3. 国网北京经济技术研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 September 2019,
Published:2019
稿件说明:
移动端阅览
WANG Yunchao, YU Zhanqing, JI Yiming, et al. Breaking Characteristics of AC-filter Breaker for UHVDC with Hierarchical Connection to AC Grid[J]. 2019, 45(9): 2857-2865.
DOI:
WANG Yunchao, YU Zhanqing, JI Yiming, et al. Breaking Characteristics of AC-filter Breaker for UHVDC with Hierarchical Connection to AC Grid[J]. 2019, 45(9): 2857-2865.DOI:
Breaking Characteristics of AC-filter Breaker for UHVDC with Hierarchical Connection to AC Grid
When a UHVDC project is hierarchically connected to AC grid
the performance of AC-filter breaker significantly influences the operation reliability. To study the breaking characteristics of the AC filter breaker of ±800 k V UHVDC hierarchical connection to AC grid
a circuit analysis model is established. It is concluded that when a DC line ground fault occurs and all AC filters need to be removed under the bipolar operation mode
the break recovery voltage peak value between the AC-filter breaker reaches the maximum. When all AC filters are removed during a ground fault in the AC net
the breaking current peak value is the highest. As the filter reactive power capacity increases
the breaking current of the circuit breaker increases. When cutting off a large group of filters of the same capacity
the breaking current under the small operation mode is greater than the one under the large operation mode. Under the same operation mode
the peak break recovery voltage is similar when filter groups with different capacity are cutting off. It is verified that the break recovery voltage is mainly related to the system operation mode and the AC bus voltage