Extraction of New Characteristic Parameters and Aging Diagnosis for Transformer Oil-paper Insulation Based on Terminal Two-point Analytical Method
|更新时间:2025-12-08
|
Extraction of New Characteristic Parameters and Aging Diagnosis for Transformer Oil-paper Insulation Based on Terminal Two-point Analytical Method
Vol. 45, Issue 10, Pages: 3317-3326(2019)
作者机构:
福州大学电气工程与自动化学院福建省新能源发电与电能变换重点实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 October 2019,
Published:2019
稿件说明:
移动端阅览
ZHANG Xiaoyan, LIU Qingzhen, CAI Jinding. Extraction of New Characteristic Parameters and Aging Diagnosis for Transformer Oil-paper Insulation Based on Terminal Two-point Analytical Method[J]. 2019, 45(10): 3317-3326.
DOI:
ZHANG Xiaoyan, LIU Qingzhen, CAI Jinding. Extraction of New Characteristic Parameters and Aging Diagnosis for Transformer Oil-paper Insulation Based on Terminal Two-point Analytical Method[J]. 2019, 45(10): 3317-3326.DOI:
Extraction of New Characteristic Parameters and Aging Diagnosis for Transformer Oil-paper Insulation Based on Terminal Two-point Analytical Method
In the research of time-division dielectric response for oil-paper transformer insulation aging diagnosis
there always exists uncertainty in the solution spectrum of the dielectric response spectra
the parameter calculation process is complex
and it is difficult to describe the physical meaning of the indirect extracted feature quantity. In accordance with the problem in the circuit model determination and the feature extraction
we propose a new method to diagnose the aging condition for transformer oil-paper insulation. Firstly
a terminal two-point analytical method of depolarization current spectrum is put forward to determine the insulation equivalent circuit for transformer oil-paper insulation
a new type of polarization maximum straight spectrum is drawn
and three new characteristic parameters
such as
the number of polarization low resistances lLow
R
the maximum slope of polarization aτmax
and the maximum intercept of polarization bτmax
are directly extracted. It is confirmed that
the more serious the aging of oil-paper insulation is
the larger the number of lLow
R
will be
and the greater value of aτmax and bτmax will be. The analysis and calculation of experimental data of several transformers prove that the aging status for transformer oil-paper insulation can be effectively diagnosed through new characteristic parameters. The new method and characteristic quantity of equivalent circuit provide a new way to diagnose the aging of oil-paper insulation.