Fast Identification of Abnormal State Based on Kernel Principal Component Analysis for Oil Chromatography Analysis On-line Monitoring Device
|更新时间:2025-12-08
|
Fast Identification of Abnormal State Based on Kernel Principal Component Analysis for Oil Chromatography Analysis On-line Monitoring Device
Vol. 45, Issue 10, Pages: 3308-3316(2019)
作者机构:
1. 新能源电力系统国家重点实验室(华北电力大学)
2. 国网山东省电力公司电力科学研究院
3. 广东电网有限责任公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 October 2019,
Published:2019
稿件说明:
移动端阅览
RONG Zhihai, QI Bo, ZHANG Peng, et al. Fast Identification of Abnormal State Based on Kernel Principal Component Analysis for Oil Chromatography Analysis On-line Monitoring Device[J]. 2019, 45(10): 3308-3316.
DOI:
RONG Zhihai, QI Bo, ZHANG Peng, et al. Fast Identification of Abnormal State Based on Kernel Principal Component Analysis for Oil Chromatography Analysis On-line Monitoring Device[J]. 2019, 45(10): 3308-3316.DOI:
Fast Identification of Abnormal State Based on Kernel Principal Component Analysis for Oil Chromatography Analysis On-line Monitoring Device
The health status of power transformers can be effectively reflected by on-line monitoring the dissolved gas in oil. However
if the monitoring device works in abnormal conditions
it is difficult to ensure the accuracy of the condition assessment. At present
tedious manual on-site verification is adopted to identify abnormal monitoring devices
it is hard for the criterion fusion method to identify minor step anomaly
and it takes a long time to complete the identification. To settle the problems
we put forward an abnormally fast identification method of dissolved gas device based on Kernel Principal Component Analysis(KPCA).This method can be adopted to identify abnormal data quickly according to Hotelling-T2 and Squared Prediction Error statistics and identify abnormal types with abnormal data characteristics. The test results show that KPCA can be adopted to effectively identify step mutation anomalies with a minimum amplitude of 5% that are difficult to be recognized by threshold method. To identify the abnormal working state of 677 monitoring devices in a regional power grid with this method
the test accuracy rate is 95.7%
which is not far from accuracy of the criterion fusion method 96.9%
but the time consuming is far less than that by the criterion fusion method. Therefore
the abnormal state of dissolved gas in oil monitoring devices can be identified quickly when the accuracy is not significantly reduced.