Study on the Disturbance for Power Port of Intelligent Component Caused by Ground Potential Rise During Transformer Lightning Impulse Tests
|更新时间:2025-12-08
|
Study on the Disturbance for Power Port of Intelligent Component Caused by Ground Potential Rise During Transformer Lightning Impulse Tests
Vol. 46, Issue 1, Pages: 303-311(2020)
作者机构:
1. 华北电力大学电力工程系
2. 中国电力科学研究院有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 January 2020,
Published:2020
稿件说明:
移动端阅览
JING Yongming, GAO Fei, LIU Xin, et al. Study on the Disturbance for Power Port of Intelligent Component Caused by Ground Potential Rise During Transformer Lightning Impulse Tests[J]. 2020, 46(1): 303-311.
DOI:
JING Yongming, GAO Fei, LIU Xin, et al. Study on the Disturbance for Power Port of Intelligent Component Caused by Ground Potential Rise During Transformer Lightning Impulse Tests[J]. 2020, 46(1): 303-311.DOI:
Study on the Disturbance for Power Port of Intelligent Component Caused by Ground Potential Rise During Transformer Lightning Impulse Tests
In accordance with the fault that the power port of intelligent components often fails to work or is destroyed in th process of lightning impulse tests
the electromagnetic disturbance characteristics of power port were researched by experiments and measurements. According to the circuit connection of a test hall
the reason of the ground potential rise(GPR) was analyzed by measuring the loop currents. Results show that the high frequency capacitive current flows into ground will result in GPR
and the inductive impedance of ground wire leads to the difference in large ground potentials. To accurately measure in the complex measuring environment in testing hall and substation
the measure system was developed
which is able to avoid the space electromagnetic disturbance and circuit conduction disturbance. The voltages of power port were acquired and analyzed in time-domain and frequency-domain. Results show that
in the absence of surge protection device(SPD)
the common-mode disturbance is more than 20 kV
which is much higher than specified value(4 kV) in IEC61000-4-5. When SPD is connected
the common-mode disturbance can be restrained to 4 kV and the difference mode disturbance can be restrained to 2 kV. The conclusion in this paper can provide a reference to resist electromagnetic disturbance for intelligent components.