Phase-locked loop(PLL) is commonly used in doubly-fed induction generator(DFIG) for its grid synchronization by tracking the phase angle of turbine terminal voltage; however a DFIG which is connected to weak grids by a synchronization technique will lead to instability. Consequently
we try to uncover the mechanism of phenomenon of instability. In non-ideal grid connection
terminal voltage phase angel is affected by the power outputs of DFIG
resulting in a dynamic coupling between PLL and DFIG power controls. Considering such a coupling effect
we propose a reduced small-signal model for a single DFIG infinite bus system. Based on this model
it is found that
owing to the coupling relation within active power and terminal voltage magnitude
an addition positive feedback branch is introduced to the PLL
and the loop gain increases as the system strength decreases
thus the stability of DFIG under weak grid operating conditions is deteriorated. Moreover
for open-loop terminal voltage control condition
the stability margin is analytically derived. Furthermore
the impact of terminal voltage control is also qualitatively analyzed. Full-order time-domain simulations are conducted to verify the effectiveness of the proposed simplified model and correlated analysis.