Application of Superconducting Magnetic Energy Storage-current Limiter to Improve the Transient Stability of Photovoltaic Grid-connected Power Generation System
|更新时间:2025-12-08
|
Application of Superconducting Magnetic Energy Storage-current Limiter to Improve the Transient Stability of Photovoltaic Grid-connected Power Generation System
Vol. 46, Issue 1, Pages: 90-99(2020)
作者机构:
1. 四川大学电气工程学院
2. 国网四川省电力公司成都供电公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 January 2020,
Published:2020
稿件说明:
移动端阅览
LI Yongkai, LEI Yong, LIN Xiaodong. Application of Superconducting Magnetic Energy Storage-current Limiter to Improve the Transient Stability of Photovoltaic Grid-connected Power Generation System[J]. 2020, 46(1): 90-99.
DOI:
LI Yongkai, LEI Yong, LIN Xiaodong. Application of Superconducting Magnetic Energy Storage-current Limiter to Improve the Transient Stability of Photovoltaic Grid-connected Power Generation System[J]. 2020, 46(1): 90-99.DOI:
Application of Superconducting Magnetic Energy Storage-current Limiter to Improve the Transient Stability of Photovoltaic Grid-connected Power Generation System
摘要
针对光伏并网发电系统转动惯量小
在受到不同的干扰时容易脱网运行的问题
提出了一种基于超导磁储能—限流器(superconducting magnetic energy storage-fault current limiter
In order to solve the problems that the instantaneous inertia of photovoltaic(PV) grid-connected power generation system is small and is easy to off-grid when suffering from different disturbances
a control strategy of a superconducting magnetic energy storage-fault current limiter(SMES-FCL) device is proposed to improve the transient stability of PV grid-connected power generation system. The SMES-FCL device is connected in series at the common coupling point between PV power station and distribution network through three-phase transformer
which has dual functions of current limiting and energy storage. However
due to the high-intensity nonlinearity and coupling of the SMES-FCL system
a double closed-loop sliding-mode control(SMC) method is adopted. SMC is used to stabilize the DC side bus voltage in the outer ring
and in the inner ring SMC is used to achieve rapid decoupling of current. The effectiveness of the control strategy is verified through simulations. The simulation results show that adding SMES-FCL devices outside can improve the fault-ride through(FRT) ability of PV grid-connected power generation system effectively
and reduce the impact of power fluctuations on the distribution network. Compared with PI control strategy
the proposed SMC control strategy enhances the disturbance resistance of SMES-FCL.