Development of Online Monitoring Device of Transformer Bushing Based on Inner Pressure Response
|更新时间:2025-12-08
|
Development of Online Monitoring Device of Transformer Bushing Based on Inner Pressure Response
Vol. 46, Issue 2, Pages: 569-575(2020)
作者机构:
1. 国网四川省电力公司电力科学研究院
2. 国网四川省电力公司
3. 国网攀枝花供电公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:29 February 2020,
Published:2020
稿件说明:
移动端阅览
CHEN Ling, SU Changhua, WU Xiaohui, et al. Development of Online Monitoring Device of Transformer Bushing Based on Inner Pressure Response[J]. 2020, 46(2): 569-575.
DOI:
CHEN Ling, SU Changhua, WU Xiaohui, et al. Development of Online Monitoring Device of Transformer Bushing Based on Inner Pressure Response[J]. 2020, 46(2): 569-575.DOI:
Development of Online Monitoring Device of Transformer Bushing Based on Inner Pressure Response
The discharge defects in oil-paper bushing can not be timely discovered due to lack of effective online monitoring method
thus explosion on bushing occasionally occurs. In order to provide an effective online monitoring device to find the discharge defects in oil-paper bushings
we researched the influences of characteristic gases produced in bushing on the inner pressure of bushing
and developed an online monitoring device based on inner pressure response. Moreover
we analyzed the sensitivity of the online device in finding discharge defect
and verified the validity of the online monitoring device by partial discharge(PD) tests performed on real bushing. The results show that characteristic gases such as hydrogen
methane
and carbon monoxide produced by discharge defects of oil-paper insulation can cause significant increase in the internal pressure
and the internal pressure will increase with the development of defects. The method to monitor the pressure of bushing is available to discover discharge defect in busing
and the online monitoring device developed in this paper has sufficient sensitivity to discover initial discharge defect in bushing. Therefore
the on-line monitoring device developed in this paper can be used to realize the defect warning of oil-paper insulating bushing