Pollution Distribution Characteristic of Epoxy Insulator on Electric Multiple Units Roof in 200 km/h High Speed Wind Tunnel
|更新时间:2025-12-08
|
Pollution Distribution Characteristic of Epoxy Insulator on Electric Multiple Units Roof in 200 km/h High Speed Wind Tunnel
Vol. 46, Issue 3, Pages: 1005-1012(2020)
作者机构:
1. 兰州交通大学自动化与电气工程学院
2. 河北省输变电安全防御重点实验室(华北电力大学)
3. 国网电力科学研究院武汉南瑞有限责任公司
4. 甘肃省轨道交通电气自动化工程实验室
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 March 2020,
Published:2020
稿件说明:
移动端阅览
MA Jianqiao, SUN Zhenlong, Lü Fangcheng, et al. Pollution Distribution Characteristic of Epoxy Insulator on Electric Multiple Units Roof in 200 km/h High Speed Wind Tunnel[J]. 2020, 46(3): 1005-1012.
DOI:
MA Jianqiao, SUN Zhenlong, Lü Fangcheng, et al. Pollution Distribution Characteristic of Epoxy Insulator on Electric Multiple Units Roof in 200 km/h High Speed Wind Tunnel[J]. 2020, 46(3): 1005-1012.DOI:
Pollution Distribution Characteristic of Epoxy Insulator on Electric Multiple Units Roof in 200 km/h High Speed Wind Tunnel
Sand environment along Lanzhou-Xinjiang high-speed affects the contamination distribution on the roof insulator surface of electric multiple units(EMU)
which can result in EMU ‘break down’ faults under humid climate conditions. In a closed wind tunnel
the contamination time on the surface contamination distribution of the EMU roof epoxy resin insulator at the speed 200 km/h were experimentally investigated. The results show that
the contamination distribution on insulator surfaces tends to be in fan-shaped non-uniform distribution
leeward contamination density is the heaviest
and the contamination density of top surface is greater than that of the bottom except the 7th sheath. From 2 h to 20 h
the top surface contamination density of the leeward side increases with the contamination time
increasing. When the time is 20 h
the pollution density tends to be saturated and the value can be up to 5.6 mg/cm
2
. When the leeward side number is taken as a reference
the ratio of the windward and the crossward side density to the leeward side becomes smaller with a prolongated contamination duration. The research results can provide the basis for insulator flashover tests and insulator structure optimization design under the wind sand environment of Lanzhou-Xinjiang high speed railway.