Measurement Method for the Transition Resistance of On-load Tap Changer Based on Signal Processing
|更新时间:2025-12-08
|
Measurement Method for the Transition Resistance of On-load Tap Changer Based on Signal Processing
Vol. 46, Issue 3, Pages: 922-930(2020)
作者机构:
1. 中国农业大学信息与电气工程学院
2. 河北科技师范学院机电工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 March 2020,
Published:2020
稿件说明:
移动端阅览
SONG Dongdong, DING Laiwei, DONG Biao, et al. Measurement Method for the Transition Resistance of On-load Tap Changer Based on Signal Processing[J]. 2020, 46(3): 922-930.
DOI:
SONG Dongdong, DING Laiwei, DONG Biao, et al. Measurement Method for the Transition Resistance of On-load Tap Changer Based on Signal Processing[J]. 2020, 46(3): 922-930.DOI:
Measurement Method for the Transition Resistance of On-load Tap Changer Based on Signal Processing
The on-load tap changer(OLTC) needs to be tested for working conditions by DC or AC source testing device before the ex-factory and during the maintenance period. The OLTC AC test device has problems such as inaccurate calculation of transition resistance and other information acquisition due to the large impedance of the measuring circuit. We proposed a solution method of the loop impedance by using the wavelet transform
Fourier transform
Prony algorithm to extract the base wave component of the sampled signal
and by taking the coordinate transformation of d and q as the core algorithm. Firstly
the key points of OLTC switching was identified by the wavelet transform
and then the differences between the Fourier algorithm
Prony algorithm and the least square algorithm in extracting the fundamental wave components of the signal were compared. Finally
the equivalent impedance and transition resistance of the circuit were calculated by d and q coordinate transformation. The results show that the simulation results are basically consistent with the measured results
verifying the validity of the method
and the error of the transition resistance calculated by the Fourier algorithm is the lowest
about 104.812 5%. This method provides references for optimizing the measurement of the working parameters of OLTC equipment
and can provide ideas for the next prototype development.