Effect of Structural Form on Performance of Connector Terminal in UHV DC Converter Station
|更新时间:2025-12-08
|
Effect of Structural Form on Performance of Connector Terminal in UHV DC Converter Station
Vol. 46, Issue 3, Pages: 915-921(2020)
作者机构:
中国电力科学研究院有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:31 March 2020,
Published:2020
稿件说明:
移动端阅览
ZHANG Xuesong, ZHU Kuanjun, ZHOU Lixian, et al. Effect of Structural Form on Performance of Connector Terminal in UHV DC Converter Station[J]. 2020, 46(3): 915-921.
DOI:
ZHANG Xuesong, ZHU Kuanjun, ZHOU Lixian, et al. Effect of Structural Form on Performance of Connector Terminal in UHV DC Converter Station[J]. 2020, 46(3): 915-921.DOI:
Effect of Structural Form on Performance of Connector Terminal in UHV DC Converter Station
To study the effect of structural form on the performance of the terminal connectors of UHV DC converter station
experiments and finite element calculation are carried out on the electric resistance and temperature rise of terminal connectors with different structural forms. The experimental results show that the resistance of the overlapping parts of the double-plate lap terminal connectors is lower than that of the same part of single-plate lap with the same tightening torque. With the decrease of the fastening torque
the increase of resistance of the double-plate lap terminal connectors is less than that of the single lap. The calculation results show that the temperature and the temperature rise rate of the overlapping part of the double-plate lap terminal connectors
under the same current intensity
are lower than that of the single lap
and the temperature rise rate of the terminal connectors can be reduced by increasing the fastening torque. With the decrease of section thickness
the non-linear increase of temperature rise of overlapping parts of the double-plate lap terminal connectors is less than that of the single lap. As the current intensity increases
the linear increase of temperature rise of overlapping parts of the double-plate lap terminal connectors is less than that of the single lap.
Temperature Rise Calculation of Connector Terminal in UHV DC Converter Station and Analysis of Influencing Factors
Influence of Oil-separation Rate of Electric Compound Grease on Temperature Rise of Terminal Connectors
Temperature-rise Characteristics and Optimum Design for Terminal Connectors in UHV DC Converter Station
Pollution and Water Molecule Effects on Porcelain Post Insulator Heating
Ablation Damage and Temperature Rise of Metal Oil Tanks Struck by Direct Lightning
Related Author
LIU Shengchun
WANG Fochi
MA Jianqiao
Lü Fangcheng
LIU Hongyu
GUO Yunxiang
YANG Shengjie
LIU Yakun
Related Institution
Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense,North China Electric Power University
Key Laboratory of Control of Power Transmission and Conversion, Ministry of Education, Department of Electrical Engineering of Shanghai Jiao Tong University
State Key Laboratory of Chemicals Safety, Safety Engineering Institute, China Petroleum & Chemical Corporation
School of Electrical Engineering, Shenyang University of Technology
Foshan Power Supply Company, Guangdong Power Grid Corporation