Impact of EV Charging Strategies on Ampacity and Thermal Life of Distribution Cables with Consideration of Harmonic Distortions
|更新时间:2025-12-08
|
Impact of EV Charging Strategies on Ampacity and Thermal Life of Distribution Cables with Consideration of Harmonic Distortions
Vol. 46, Issue 4, Pages: 1269-1280(2020)
作者机构:
1. 中国电力科学研究院有限公司电网环境保护国家重点实验室
2. 武汉大学电气与自动化学院
3. 国网江苏省电力有限公司苏州供电分公司
4. 4. 武汉易摩特科技有限公司
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 April 2020,
Published:2020
稿件说明:
移动端阅览
MENG Shaoxin, QIAN Kejun, WANG Hang, et al. Impact of EV Charging Strategies on Ampacity and Thermal Life of Distribution Cables with Consideration of Harmonic Distortions[J]. 2020, 46(4): 1269-1280.
DOI:
MENG Shaoxin, QIAN Kejun, WANG Hang, et al. Impact of EV Charging Strategies on Ampacity and Thermal Life of Distribution Cables with Consideration of Harmonic Distortions[J]. 2020, 46(4): 1269-1280.DOI:
Impact of EV Charging Strategies on Ampacity and Thermal Life of Distribution Cables with Consideration of Harmonic Distortions
In order to avoid overloading of distribution cables dues to electric vehicles(EVs) charging and determine suitable ampacity
this paper presents a methodology for modeling and analyzing the cable temperature and thermal life when EVs are charged using four strategies
e.g. low/high power uncontrolled domestic charging and off-peak domestic charging. The model is formulated to predict the current of distribution cable by taking into account the stochastic nature of the charging power
start time of individual charging
and harmonic wave characteristic. Then
analytical solution of the cable temperature is deduced based on IEC 60287 equations
and the influences of harmonic waves on additional AC resistance of conductors
hysteresis loss and eddy current loss of armor layer are analyzed. Finally
thermal life of distribution cable is predicted by Arrhenius model(AM). A typical distribution system with residential load ratio of 0.7 is adopted as an example of simulation. The results of a 30% penetration of EVs in the simulation show that the temperature of distribution cable will increase by 26.19 ℃
and will increase by 20.89 ℃ if the harmonic wave is not taken into consideration. The contribution of harmonic waves to the temperature increment is 20.17%. High power uncontrolled domestic charging will result in overloading of distribution cable at a 30% penetration level in summer. Low power off-peak domestic charging is the recommended as a charging strategy with the lowest cable temperature