Optimal Siting and Sizing Method of Soft Open Point in Distribution Network Combined with Traditional Regulations
|更新时间:2025-12-08
|
Optimal Siting and Sizing Method of Soft Open Point in Distribution Network Combined with Traditional Regulations
Vol. 46, Issue 4, Pages: 1181-1189(2020)
作者机构:
1. 浙江大学电气工程学院
2. 国网浙江省电力有限公司
3. 国网浙江省电力有限公司电力科学研究院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 April 2020,
Published:2020
稿件说明:
移动端阅览
CHEN Yaoyu, GENG Guangchao, JIANG Quanyuan, et al. Optimal Siting and Sizing Method of Soft Open Point in Distribution Network Combined with Traditional Regulations[J]. 2020, 46(4): 1181-1189.
DOI:
CHEN Yaoyu, GENG Guangchao, JIANG Quanyuan, et al. Optimal Siting and Sizing Method of Soft Open Point in Distribution Network Combined with Traditional Regulations[J]. 2020, 46(4): 1181-1189.DOI:
Optimal Siting and Sizing Method of Soft Open Point in Distribution Network Combined with Traditional Regulations
Soft open point(SOP) is a new kind of flexible equipment in the distribution network. Under reasonable site selection and capacity planning
it can significantly promote feeder balance
reduce transmission loss
and enhance new energy consumption
so it is crucial to carry out reasonable site selection and capacity planning for SOPs. In this paper
a three-layer planning model for the location and capacity of SOPs is proposed: the top layer determines the installation location and capacity
and passes them to the middle layer; then the middle layer uses simulated annealing algorithm to determine the operational condition of traditional regulations such as on-load tap changers(OLTC) and reactive compensation capacitors; the bottom layer solves the operation conditions of SOPs by particle swarm optimization algorithm. Furthermore
the power transmission distribution factors and incremental rate of power loss are proposed in this paper
which effectively reduce the complexity of the three-layer model. Finally
the case of IEEE33 distribution network shows that the proposed model can effectively determine the location and capacity of SOPs
and can give the joint operation conditions of SOPs and traditional regulations
which significantly reduce the operating costs of the distribution network. Therefore
it is necessary to consider the mutual coordination of SOPs and traditional regulations in order to minimize investment cost and improve operational economic benefits.