Structural Design of Arc Extinguisher for Dual-energy SF6 High Voltage Circuit Breaker and Simulation Research of Its Arc-extinguishing Characteristics
|更新时间:2025-12-08
|
Structural Design of Arc Extinguisher for Dual-energy SF6 High Voltage Circuit Breaker and Simulation Research of Its Arc-extinguishing Characteristics
Vol. 46, Issue 6, Pages: 2040-2048(2020)
作者机构:
山东理工大学电气与电子工程学院
作者简介:
基金信息:
DOI:
CLC:
Published Online:30 June 2020,
Published:2020
稿件说明:
移动端阅览
JIANG Renzhuo, HE Baina, XIE Yadi, et al. Structural Design of Arc Extinguisher for Dual-energy SF6 High Voltage Circuit Breaker and Simulation Research of Its Arc-extinguishing Characteristics[J]. 2020, 46(6): 2040-2048.
DOI:
JIANG Renzhuo, HE Baina, XIE Yadi, et al. Structural Design of Arc Extinguisher for Dual-energy SF6 High Voltage Circuit Breaker and Simulation Research of Its Arc-extinguishing Characteristics[J]. 2020, 46(6): 2040-2048.DOI:
Structural Design of Arc Extinguisher for Dual-energy SF6 High Voltage Circuit Breaker and Simulation Research of Its Arc-extinguishing Characteristics
To meet the requirements of rapid cut-off and protection of modern power grids
SF
6
high-voltage circuit breakers are the main type of line protection devices
and their arc-extinguishing performance needs to be strengthened. Aiming at the reaction time difference of the current self-energizing SF
6
high voltage circuit breaker during arc extinguishing
we proposed a new type of an arc-extinguishing chamber structure with piston-assisted air dual-energy SF
6
high-voltage circuit breaker;moreover
taking the structure as a research object
on the basis of analyzing the formation and arc extinguishing mechanism of the dual-energy strengthenin
g airflow
we established an airflow field model and arc model of the arc-extinguishing process. The Fluent software was used to simulate the temperature field of the arc-coupled airflow during the arc-enhanced airflow interception arc. The simulation results show that the dual-energy arc-extinguishing chamber structure proposed in this paper can extinguish the power-frequency arc within 5 ms when it is applied to the 110 kV voltage level for arc extinguishing
and can effectively suppress the secondary arcing between the arc contacts in the subsequent time. The arc extinguishing chamber structure can continue to maintain a cold airflow in the arc extinguishing passage after the arc is extinguished
and can quickly reduce the arcing residual temperature in the thermal expansion chamber. The research results in this paper can provide a technical reference for improving the breaking capacity of SF